Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

1.4 STANDARDS<br />

The applicable provisions of the following standards shall apply as if written here in their<br />

entirety:<br />

ASTM A-126 Specification for Gray Iron Castings for Valves, Flanges and Pipe Fittings<br />

ASTM B-61 Specification for Steam and Valve Bronze Castings<br />

1.5 JOB CONDITIONS<br />

A. SPECIAL TOOLS: Furnish a kit which contains special size wrenches and other types of<br />

tools, not normally available, which are necessary for assembling, disassembling,<br />

aligning, and calibrating each piece of equipment. In addition, any piece of equipment<br />

(meter, test set, etc.) required by the Manufacturer to align, adjust, or otherwise calibrate<br />

any item under this section of the specification shall be furnished, including software.<br />

PART 2 PRODUCTS<br />

2.1 ELECTROMAGNETIC FLOW TRANSMITTER<br />

A. Flow element shall be of the electromagnetic type utilizing the pulsed DC type coil<br />

excitation principle with high preamp input impedance. The flow measuring system,<br />

consisting of low element, transmitter, and appurtenances, shall have an overall accuracy<br />

of ±.25% of rate with a 10:1 turndown for all flows resulting from pipe velocities of 1' to<br />

31' per second. Stream fluid meter size and flow range shall be as noted. Unit shall have<br />

zero stability feature thereby eliminating the need to stop flow to check zero alignment.<br />

B. The flow element shall be of water-tight, NEMA 6 construction for submersible<br />

applications. Meter shall consist of a 304 stainless steel meter tube, 150 pound ANSI<br />

carbon steel raised-face flanges, ebonite hard rubber liner, and Hastelloy electrodes,<br />

unless otherwise noted. Electrodes shall be either flush or bullet nose type. Suitable<br />

covers shall be provided for flow elements ends to protect the tube liner during shipment.<br />

Liners for magnetic flow meters shall be neoprene.<br />

C. Flow transmitter shall be enclosed and water-tight, NEMA 4X construction for outdoor<br />

installation and mounted on the flow meter. The transmitter output shall be a 4-20 mA<br />

DC signal in linear proportion to flow and shall dive loads with impedances in the range<br />

of 0 to 800 ohms without load adjustments for a 24V DC supply. Output span and zero<br />

shall be manually adjustable. Both transmitter and primary element shall be powered<br />

from the same 120 volt, 60 Hz source.<br />

D. Provide an isolation kit for the flow meter.<br />

E. The flow meter shall come with the required amount of manufacturer’s supplied cable for<br />

routing the signal from the flow element to the transmitter. See plans for location of flow<br />

meter and transmitter. Manufacturer’s supplied cable shall be one continuous cable. No<br />

splicing allowed. Special cables shall be installed in conduit. Cable(s) shall facilitate<br />

both signal and power for the flow element (120 volt, 60 Hz power will be made<br />

available at the transmitter).<br />

May 18, 2012<br />

Instrumentation Flow Meters<br />

Revision 0 40 90 01.01-4