C. Post-submittal Sample Screens for Graphic User Interface (GUI) Touch Screen meeting:<br />

SCADA Installer shall include in his bid the cost of attending a one-day post-submittal<br />

meeting to go over the Sample Screens for the Touchscreens in the offices of Freese and<br />

Nichols, in Fort Worth, Texas or at the CRMWD office in Big Spring, Texas (location to be<br />

determined at the Pre-Submittal Shop Drawing meeting). The Project Manager for the<br />

SCADA System Installer must be present. A sales person may attend, but not as a<br />

substitute for the Project Manager. SCADA System Installer shall determine the number<br />

of people attending the meeting and cover each person’s cost.<br />

D. Loop diagrams shall be prepared according to ISA Standard ISA-S5 and using loop numbers<br />

provided.<br />

E. Shop Drawings:<br />

1. Schematic ladder diagrams shall include all terminal blocks, hardware devices, software<br />

interlocks, software data links, and control.<br />

2. Drawings, Diagrams & Schematics shall be on 11x17 paper<br />

a. PLC panel layout, plans, elevations, sections, details, etc.<br />

b. A schedule defining all I/O, database reference, and point of origin or destination,<br />

and PLC system internal address.<br />

c. I/O Drawings shall show where the signal originates from the left side with the<br />

destination on the right. For example, PLC input cards shall be on the right side<br />

with the field device on the left. All I/O associated with a I/O card shall be shown<br />

on the a single sheet. Each field device shall be identified by instrument tag, loop<br />

number, and instrument range (if applicable).<br />

d. Elevation drawings shall include mounting heights of panel mounted devices<br />

including but not limited to the HMI Touchscreen, indication lights, switches, etc.<br />

3. Software manuals shall be provided to configure the central system and technical<br />

review information. Provide sample program documentation from previous projects.<br />

4. Hard Copy of software program including programs and rung comments<br />

5. UPS Battery Sizing Calculations<br />

6. Radio Path Study Results<br />

a. The radio path study shall include a summary page indicating the findings and<br />

recommendations. The radio path study shall include information from both the<br />

software path study and from the physical radio path study test.<br />

b. The radio path study shall include screen shots from the radio path software study.<br />

7. Sample screens for the graphic user interface Touch Screens shall be submitted to the<br />

Owner/Engineer for approval.<br />

1<br />

Supervisory Control and Data Acquisition (SCADA) System 40 90 02-7<br />

CMD11269 – Ward County Transmission System Expansion – Contract C – Above Slab TPS, OPS, and WPS