Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

C. RIGID STEEL CONDUIT: Heavy wall, mold steel tube with metallic, corrosion<br />

resistant coating on interior and exterior, hot dipped galvanized steel, free from defect;<br />

manufactured in accordance with FED. Spec. WW-C-581, ANSI C80.1 standards, and<br />

U.L. listed. Acceptable manufacturers shall be Allied, Triangle, and Wheatland.<br />

D. PVC COATED RIGID ALUMINUM: Meeting the requirements of rigid aluminum<br />

conduit; 40 mil PVC exterior coating and 2 mil urethane interior coating, U.L. 6A listed.<br />

Acceptable Manufacturers shall be Rob Roy Plastibond Red, Ocal and Perma-Cote.<br />

E. PVC COATED RIGID STEEL: Heavy wall, mild steel tube with metallic, corrosionresistant<br />

coating on interior and exterior, hot-dipped, galvanized steel, free from defects<br />

rigid steel conduit; 40 mil PVC, exterior coating and 2 mil urethane interior coating;<br />

manufactured in accordance with Fed. Spec. WW-C-581, ANSI C80.1 standards, and<br />

U.L. listed. Acceptable Manufacturers shall be Rob Roy Plastibond Red, Ocal and<br />

Perma-Cote.<br />

F. RIGID NONMETALLIC CONDUIT: Schedule 40 high impact, polyvinylchloride, in<br />

accordance with Fed. Spec. W-C-1094 and U.L. listed. Acceptable manufacturers shall<br />

be Carlon, Cantex, and Certainteed.<br />

G. FITTINGS AND CONDUIT BODIES:<br />

1. RIGID METAL CONDUIT: Threaded type material to match the conduit, in<br />

accordance with ANSI/NEMA FB1 and as manufactured by Appleton Form 35,<br />

Killark "O" Series, Crouse Hinds, OZ Gedney, or RACO.<br />

2. FLEXIBLE AND LIQUID TIGHT FITTINGS: In accordance with<br />

ANSI/NEMA FB1; cadmium-plated, malleable iron body and nut; aluminum<br />

ferrule; insulated throat; integrally-cast, external ground lugs, as manufactured by<br />

Appleton "ST" series, Hubbel, OZ Gedney Type 4QL, or RACO.<br />

3. PVC CONDUIT: Solvent-welded, slip-on joints, in accordance with NEMA<br />

TC3, as manufactured by Carlon, CertainTeed.<br />

4. CONDUIT SEALS: Explosion-proof, rigid metal conduit fitting as defined by<br />

NEC Article 500, and as manufactured by Crouse Hinds fitting with Chico "X"<br />

Fiber and Chico "A" compound or Appleton fitting with Apelco fiber and<br />

compound. Seal shall be same material as conduit.<br />

H. ELBOW AND BENDS: Rigid, nonmetallic conduit system shall use PVC-coated rigid<br />

steel for conduits 2" and larger for all bends greater than 45 degrees. Meeting the<br />

requirements of rigid steel conduit; 40 mil PVC, exterior coating and 2 mil urethane<br />

interior coating. Acceptable Manufacturers shall be Rob Roy Plastibond Red, Ocal and<br />

Perma-Cote. Other conduit systems shall use the same material as the conduit with<br />

which they are installed.<br />

I. BUSHINGS: High impact, thermosetting, phenolic insulation; 150 degrees C.; as<br />

manufactured by Appleton "BBUH", Blackburn, or OZ Gedney type A.<br />

J. GROUNDING BUSHINGS: Conduit grounding bushings shall consist of an aluminum,<br />

insulated throat conduit bushing with an attached aluminum set screw lug. Grounding<br />

bushing shall comply with Fed. Spec. W-F-4<strong>08</strong>b and W-W-C-581d, UL Standards 514B<br />

and 467, and shall be Crouse Hinds Lazy Lug or approved equal.<br />

May 18, 2012<br />

Conduits<br />

Revision 0 26 05 33.01 - 2