. Memory battery backup shall be capable of 14 days memory retention after the<br />

"Battery Low" indicating LED is on.<br />

6. Plug-in card design to allow quick field replacement of fault devices.<br />

a. Provide unit designed for field replacement and expansion of memory without<br />

requiring rewiring or use of special tools.<br />

7. 100 percent minimum spare useable memory capacity after all required programming is<br />

in place and operating.<br />

8. Capable of executing all control functions required by the Contract Drawings including<br />

digital and analog loops.<br />

9. Built-in three-mode (proportional-integral-derivative) control capabilities.<br />

a. As directly selectable algorithms requiring no user knowledge of programming<br />

languages.<br />

10. On line reconfigurable.<br />

11. Lighted status indicators for "RUN" and "FAILURE."<br />

12. Capable of manual or automatic control mode transfer from the HMI system or from<br />

within the control strategy. Transfer shall be bumpless and balanceless.<br />

13. Modbus ports shall be provided for RS485 data highway associated with Multilin relays.<br />

See Plans for more details.<br />

B. Input/Output (I/O) Modules<br />

1. Provide plug-in modular-type I/O racks in each PLC enclosures if required, with cables to<br />

connect to all other required PLC system components.<br />

2. Provide I/O system with:<br />

a. I/O solid state boards with status lights indicating I/O status and board failure.<br />

b. Electric isolation between logic and field device.<br />

c. Individually fused outputs with blown fuses indication.<br />

d. Interchangeable boards for similar I/O type to allow substitution of operating<br />

boards for failed units by the operator.<br />

e. Capability of withstanding low energy common mode transient to 1500 V without<br />

failure.<br />

f. Incorporate noise suppression design.<br />

g. Capable of meeting or exceeding surge-withstand capability tests, per ANSI/IEEE<br />

C37.90.1.<br />

h. Capable of meeting or exceeding electrical noise tests, NEMA ICS1-109.60-109.66.<br />

i. Capable of being removed and inserted into the I/O rack under power, without<br />

affecting any other I/O modules in the rack.<br />

3. Discrete I/O Modules:<br />

a. Interface to ON/OFF devices<br />

b. I/O status indicator module front<br />

c. Voltage rating to match circuit voltage<br />

d. Output module current rating:<br />

1) Match maximum circuit current draw<br />

2) Minimum 1.5 A/point for 120 V AC applications<br />

e. Isolated modules for applications where one module interfaces with devices<br />

utilizing different sources of power.<br />

f. Individually fused with blown fuse indication.<br />

Supervisory Control and Data Acquisition (SCADA) System 40 90 02-16<br />

CMD11269 – Ward County Transmission System Expansion – Contract C – Above Slab TPS, OPS, and WPS