BID ADDENDUM<br />

FAILURE TO RETURN THIS BID ADDENDUM IN ACCORDANCE WITH INSTRUCTIONS<br />

MAY SUBJECT YOUR BID TO REJECTION ON THE AFFECTED ITEM(S)ISERVICES.<br />

Project Number: WRJ 1.0143<br />

Description: Vertical Turbine Submersible Pumping Units<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

Addendum Number: 1<br />

Date: January 19, 2012<br />

will constitute rejection of the equipment.<br />

ii) Delete Paragraph 1 I.E in its entirety and replace with the following:<br />

E. The pumping units will be started across the line at 480 V, 3 phase, 60 Hz.<br />

iii) Delete Paragraph 2.l.A in its entirety and replace with the following:<br />

A. The pump shall be a submersible deep well turbine type multistage in series<br />

design, complete with motor, power cable, power cable terminus to motor,<br />

transition piece at pump discharge, column pipe, discharge elbow and al1<br />

appurtenances in accordance with these specifications. The pump shall conform to<br />

A WW A El 02-06 except as otherwise specified herein. Pumping unit speed shall<br />

not exceed 1 ,800 rpm. The pump and motor shall be coupled via a positive<br />

locking stainless steel coupling to produce maximum performance for torque and<br />

thrust.<br />

iv) Delete Paragraph 2.1 G.l in its entirety and replace with the following:<br />

Execute Addendum:<br />

The submersible motor shall be designed to deliver continuously the necessary<br />

brake horse power (bhp) having a minimum 1 15 service factor The motor shaH<br />

be designed to operate at maximum of 1,800 rpm, at 480 V, 3 phase, 60 Hz,<br />

alternating current, with full voltage (across the line) starting capability with a<br />

maximum current inrush of 500% without use of special starting equipment. The<br />

motor shalt be a high reactance type design that will provide an inrush current that<br />

is low enough to allow across the line starting. The entire motor shall incorporate<br />

an insulation of Class B or better Motor shall have a NEMA code letter of E or<br />

less (i.e., locked motor KVA per horsepower shall be 5.0 or less). Motor<br />

enclosure classification shall meet or exceed IP68 requirements.<br />

<strong>Bid</strong>der: Q_\OJ.)e.., -~ eo\IXM C\- 1:.1 Pa..CJ.o I L LC.-<br />

Authorized Signature:<br />

# .iJ,_,.._ Ci ·lr-:1<br />

Name and Title (Printed): J4JYO [)... ~\COV\ {