25.10.2014 Views

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

Bid Package 08 North Well Field - Garney Construction

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

B. ENCLOSURES: NEMA 4X, 304 stainless steel for all locations. Furnish enclosures<br />

with interlocking covers with maintenance defeat feature and external front-operated<br />

flange-mounted switch levers. Disconnects shall have provisions for the use of three (3)<br />

safety padlocks in the "Off" position. Furnish horsepower rated switches for motor<br />

circuits. The fuse interrupting rating shall be 65,000 rms amperes.<br />

PART 3 EXECUTION<br />

3.1 INSTALLATION<br />

A. Install disconnect switches as required by the National Electrical Code. Install fuses in<br />

fusible disconnect switches.<br />

END OF SECTION<br />

May 18, 2012<br />

Enclosed Switches and Circuit Breakers<br />

Revision 0 26 28 16-2