electric service conductors from a Company designated point of delivery outside of<br />

the building (either secondary transformer terminals or service enclosure) to the<br />

metering equipment location. See Figure 5-A for typical point of delivery (P.O.D.)<br />

locations. Metering equipment locations other than outside the building are nonstandard<br />

and require Company approval prior to installation of the meter.<br />

Meterbases and transockets are not to be installed on Company poles. This<br />

applies to both overhead and underground services.<br />

500.05 Meter Work Space<br />

Sufficient space in front of, above, below and on each side of meter sockets,<br />

service enclosures, meterpacks and transockets is necessary for work space for<br />

connecting and the reading of meters. No obstruction shall be within four feet in<br />

front of the meter. See NEC Article 110.26 for working spaces.<br />

500.06 Meter Sockets<br />

The Customer will provide, install, and maintain self contained meter sockets.<br />

Transockets, when required, will be provided by Company and installed and<br />

maintained by Customer. These sockets are to be used exclusively for metering.<br />

The Company reserves the right to refuse service if the incorrect socket is installed<br />

or if the socket is not wired correctly. Each connector provided in the meter<br />

socket is rated for a single aluminum or copper conductor. The number of<br />

Customer conductors shall not exceed the number of connectors (shall not<br />

double lug). See Figure 5-B, pages 46-50. Aluminum conductors require wire<br />

brushing to remove oxide film and an application of oxide inhibitor immediately<br />

before installation.<br />

500.06.01 Meter Socket Ratings<br />

Meter sockets are specified by their continuous current rating and are designed<br />

for short term (three hours or less) overloads of 125%. Electrical panels are<br />

specified by their maximum rating and any continuous loads (three hours or<br />

more) are limited to 80% of this maximum. A 320 ampere meter socket has a<br />

continuous rating of 320 amperes and a maximum rating of 400 amperes. A<br />

400 ampere panel has a maximum rating of 400 amperes and a continuous<br />

rating of 320 amperes. Even though these two items are referred to by different<br />

numbers, their capabilities are identical and a 320 ampere socket is adequate<br />

to serve a 400 ampere panel.<br />

500.06.02 Ganged Meter Socket Assemblies<br />

Ganged meter socket assemblies are for multi-family residential installations<br />

and are 120/240 volt, three wire, single phase. Each of the ganged meter<br />

socket assemblies must be clearly and permanently marked to indicate each<br />

location to be served prior to the connection of service. See Figures 5-B,<br />

pages 46-50 and 5-E, page 56 for typical dimensions, examples of layouts, and<br />

terminal configurations.<br />

Copyright 2010 Oncor Electric Delivery Company. All rights reserved<br />