Colorado River Municipal Water District<br />

Raw Water Supply <strong>Well</strong> Sites<br />

Ward County <strong>North</strong> <strong>Well</strong> <strong>Field</strong><br />

B. Colors for Raceways Carrying Circuits at More Than 600 V:<br />

1. Black letters on an orange field.<br />

2. Legend: "DANGER CONCEALED HIGH VOLTAGE WIRING" with 3-inch-<br />

(75-mm-) high letters on 20-inch (500-mm) centers.<br />

C. Tape and Stencil for Raceways Carrying Circuits More Than 600 V: 4-inch- (100-mm-)<br />

wide black stripes on 10-inch (250-mm) centers diagonally over orange background that<br />

extends full length of raceway or duct and is 12 inches (300 mm) wide. Stop stripes at<br />

legends.<br />

D. Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch (50 by 50 by 1.3 mm), with stamped<br />

legend, punched for use with self-locking cable tie fastener.<br />

E. Identify each circuit with non-ferrous metal or fiber tags in manholes and junction boxes<br />

and at terminations.<br />

F. Circuits shall be tagged at terminations (both ends), in pull boxes, cabinets, and<br />

enclosures as follows:<br />

1. Tags relying on adhesives or tapes-on markers are not acceptable.<br />

2. Provide conductor tags for conductors No. 10 AWG and below with legible<br />

permanent sleeve of yellow or white PVC with machine printed black marking,<br />

Raychem TMS sleeves or approved equal.<br />

3. Provide tags for cables and for conductors No. 8 AVWG and larger consisting of<br />

permanent nylon marker plates with legible designations hot stamped on the<br />

plate. Attach these marker plates to conductors and cables with plastic wire<br />

wraps. Tags shall be Raychem TMS-CM cable markers or approved equal.<br />

4. Tags shall be imprinted with panelboard and panelboard position number (e.g.<br />

LA3-23) for conductors fed from panelboards. Other conductors shall have tags<br />

imprinted with the MCC which feeds the conductors (e.g. MCC 1).<br />

5. Switchlegs shall have the designation described above on their tags, plus an “S”<br />

suffix. Travelers shall have the designation described above on their tags, plus a<br />

“T” suffix.<br />

6. Where more than one neutral is present with a group of conductors, a tag shall be<br />

applied to each neutral indicating which phase conductors are served by each<br />

neutral (e.g. HA-2, 4, 6).<br />

2.2 CONDUCTOR IDENTIFICATION MATERIALS<br />

A. Color-coding conductor Tape:<br />

1. Colored, self-adhesive vinyl tape not less than 3 mils thick by 1 to 2 inches wide.<br />

2.3 UNDERGROUND-LINE WARNING TAPE<br />

A. Tape:<br />

1. Recommended by manufacturer for the method of installation and suitable to<br />

identify and locate underground electrical and communications lines.<br />

2. Printing on tape shall be permanent and shall not be damaged by burial<br />

operations.<br />

3. Tape material and ink shall be chemically inert, and not subject to degrading<br />

when exposed to acids, alkalis, and other destructive substances commonly found<br />

in soils.<br />

May 18, 2012<br />

Identification for Electrical Systems<br />

Revision 0 26 05 53-2