Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

• Lift heights, placement and vibration of grout.<br />

b. Inspect bond beams for compliance with Drawings and Specifications. Report on the following:<br />

• Location.<br />

• Size, placement, and lap of reinforcing bars.<br />

• Placement and vibration of group.<br />

c. Inspect openings for compliance with Drawings and Specifications. Report on following:<br />

• Types of concrete masonry units used to form lintels.<br />

• Reinforcing bar size and placement at lintels.<br />

• Stirrup size and spacing at lintels.<br />

• Vertical reinforcing size and placement at the door jambs.<br />

• Placement and vibration of grout in lintels and jambs.<br />

• Vertical reinforcing size and placement at door jambs.<br />

• Placement and vibration of gout in lintels and jambs.<br />

d. Inspect pilasters for compliance with Drawings and Specifications. Report on the following:<br />

• Vertical reinforcing size and placement.<br />

o Tie size and placement<br />

o Placement and vibration of grout.<br />

e. Inspect walls for compliance with Drawings and Specifications. Report on the following:<br />

• Spacing and grouting of embedded plates for joist bearing.<br />

• Spacing and grouting (or installation of Hilti anchors) of embedded plated for continuous<br />

angle attachment at roof perimeter.<br />

3.11 Structural Steel – (Flat Roof Building Design Projects Only):<br />

a. Inspection of columns, beams, joists and joist girders for compliance with Drawings and<br />

Specifications shall be by a structural engineer licensed in the state where the project is located.<br />

Report on the following:<br />

• Size.<br />

• Straightness.<br />

• Erection tolerances and bearing length.<br />

o Minimum 2-1/2 inch bearing length for joists.<br />

o Minimum 6 inches bearing length for joist girders.<br />

o Imperfections or damage.<br />

b. Inspection of bolted connections for placement and tightness shall be by a structural engineer<br />

licensed in the state where the project is located. High strength bolts shall be torque to a<br />

minimum value as shown in the specification for Structural Joists using A325 or A490 bolts.<br />

Report on the following:<br />

• 4 locations of joist girder to column connections shall be selected at random and checked.<br />

• 4 locations of beam to column connections shall be selected at random and checked.<br />

• 4 locations of column to footing connections shall be selected at random and checked.<br />

c. Inspect welded connections for compliance with Drawings and Specifications. Welding<br />

inspection shall be done by a Welding Inspector certified by AWS in accordance with AWS QCI<br />

Standard and Guide for qualifications and certification for welding inspectors and meeting the<br />

qualifications required of AWS D1.1. Report on the following:<br />

• 10 locations of joist to joist girder welds shall be selected at random and visually inspected<br />

for length and size of weld.<br />

• 10 locations of joist girder to column welds, when applicable, shall be selected at random<br />

and visually inspected for length and size of weld.<br />

QUALITY REQUIREMENTS 01400 - Page 10 of 11