Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

E. Finish:<br />

1. Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A<br />

525 and receive rust-inhibitive, roll coating process, including bonderizing, 0.2 mils thick<br />

baked-on prime paint, and 0.6 mils thick baked-on polyester (powder coated) top<br />

coat. Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive<br />

primer.<br />

2. Stainless Steel: Slats shall be stainless steel with 2B mill finish.<br />

F. Color: Gray polyester top coat.<br />

G. Bottom Bar: Two (galvanized) structural steel angles 1-1/2" by 1-1/2" by 1/8" minimum.<br />

H. Guides: Roll-formed steel shapes attached to continuous steel wall angle for doors thru 12' wide.<br />

1. Fastening Guides to Masonry Fire Walls: UL listed expansion anchors, or by throughbolts<br />

on soft brick or hollow block walls, or by bolts on steel jambs, or welded in<br />

accordance with manufacturer’s listing.<br />

2. Fastening Guides to Non-Masonry Fire Walls: Comply with the manufacturer’s listing.<br />

I. Brackets: Steel plate to support counterbalance, curtain and hood.<br />

J. Counterbalance: Helical torsion spring type. Counterbalance shall be housed in a steel tube or pipe<br />

barrel, supporting the curtain with deflection limited to 0.03" per foot of span. Counterbalance<br />

shall be adjustable by means of an adjusting tension wheel.<br />

K. Hood: 24 gauge galvanized primed steel minimum for wall openings thru 19' wide. Hood shall be<br />

equipped with thermally controlled, internal, galvanized steel flame baffle as required.<br />

L. Manual Operation: Manual Chain hoist.<br />

M. Automatic Closure:<br />

1. Automatic closure thermally controlled by means of 165 degree or 212 degree fusible links.<br />

2. Test and reset lever shall be provided to test release function and reset the door from the<br />

floor without tools or special training. (Test lever shall be lockable by padlock provided by<br />

others.)<br />

N. Locking interior bottom bar slide bolt.<br />

O. Wall Mounting Condition: Face-of-wall mounting.<br />

PART 3 - EXECUTION<br />

3.01 PREPARATION<br />

A. Take field dimensions and examine conditions of substrates, supports, and other conditions<br />

under which this work is to be performed. Do not proceed with work until unsatisfactory conditions<br />

are corrected.<br />

3.02 INSTALLATION<br />

A. Strictly comply with manufacturer’s installation instructions and recommendations. Coordinate<br />

installation with adjacent work to ensure proper clearances and allow for maintenance.<br />

B. Install rolling fire doors in compliance with requirements of NFPA 80. Test fire-release system and reset<br />

components after testing.<br />

C. Instruct Owner’s personnel in proper operating procedures and maintenance schedule.<br />