PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 16155<br />

EQUIPMENT WIRING<br />

PART 1 GENERAL<br />

1.01 SECTION INCLUDES<br />

A. Electrical connections to equipment.<br />

1.02 QUALITY ASSURANCE<br />

A. Conform to requirements of NFPA 70.<br />

B. Products: Listed and classified by Underwriters Laboratories, Inc. as suitable for the purpose<br />

specified and indicated.<br />

PART 2 PRODUCTS, Not Used<br />

PART 3 EXECUTION<br />

3.01 EXAMINATION<br />

A. Verify that equipment is ready for electrical connection, wiring, and start up.<br />

3.02 ELECTRICAL CONNECTIONS<br />

A. Make electrical connections in accordance with equipment manufacturer's instructions.<br />

B. Exposed conduits shall be held in place by galvanized metal straps or clips. Where grouped, they<br />

shall be neatly racked, supported by suitable trapeze or pipe ring hangers; same to be run parallel<br />

with and at right angles to beams and walls. The installation of perforated strap hangers or<br />

wire will NOT be permitted. Hangers shall be spaced not more than 5 ft. on centers.<br />

C. Where conduits terminate in panel boxes, distribution panels, switchboards, pull boxes or starter<br />

boxes, provide fiber bushing and lock nuts. Bushings shall be O.Z. Type "A" up to 2" conduit, and<br />

Type "B" over 2", or equal, Appleton or Thomas & Betts. Bushings made of thermoplastic or<br />

other flammable material are NOT acceptable.<br />

D. All conduit which enters the building through the floor or foundation walls shall enter through a hot<br />

dipped galvanized cast iron conduit entrance assembly. The shell of this fitting shall be installed in<br />

the foundation wall before the concrete is poured. Entrance seals shall be as manufactured by<br />

O.Z. Electrical Manufacturing Company, Type "FSK" or approved equal.<br />

E. All conduit entering the building below grade and terminating into panels or pull boxes will be<br />

terminated with O.Z. Electrical Manufacturing Company, Type "KR" sealing bushing.<br />

F. Final connections to all motors shall be made with flexible steel conduit. Final connections to roof<br />

exhaust fans shall be made with "Sealtite" waterproof flexible conduit. Provide additional ground<br />

wire to assure a perfect ground connection.<br />

G. No conduit will be routed on the roof.<br />

END OF SECTION<br />

EQUIPMENT WIRING 16155 - Page 1 of 1