Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

b. The cabinet shall be equipped with lock and transparent door panel providing freedom<br />

from tampering yet allowing full view of the various displays and pertinent operator<br />

controls.<br />

c. The printed circuit board assemblies of the control panel shall be mounted such that<br />

removal of a common, single piece mounting chassis shall provide access for installing<br />

the cabinet and for pulling wires into the cabinet.<br />

d. Provisions for semi-flush mounting between 24 inch center stud wall construction.<br />

e. Cabinet color shall be beige.<br />

f. To facilitate installation, the cabinet shall provide:<br />

1) Built-In depth gauges for ½ inch thick drywall installation.<br />

2) Built-In knockouts for nail holes and wiring conduit entrance.<br />

3) A built-in trim band to allow semi-flush mounting into rough cut wall openings.<br />

I. INITIATING DEVICES<br />

Locate, where shown on the drawings, the following signal initiating devices:<br />

1. Stations: Furnish and install type BG-12L double action manual pull stations with raised<br />

white lettering and a smooth high gloss finish. The break-glass station shall have a hinged<br />

front with key lock. Stations which utilize screwdrivers, allen wrenches, or other commonly<br />

available tools shall not be accepted. Stations shall be keyed alike with the fire alarm control<br />

panel. When the station is operated, the handle shall lock in a protruding manner to facilitate<br />

quick visual identification of the activated station. Provide Stopper type red wire guards<br />

where shown on drawings.<br />

2. Thermodetectors: Position white, low-profile, type 282B-PL thermodetectors rated at 194 o<br />

rate of rise and fixed temperature in all areas except where noted on the drawings, which<br />

shall be type 281B-PL rated at 135 o fixed temperature.<br />

3. Smoke Detectors: Locate type I3 Series (2W-B), ceiling mounted, photoelectric smoke<br />

detectors. Detector shall have a completely closed back to restrict entry of dust and air<br />

turbulence and 30 mesh insect screen. Electronics of unit shall be shielded to protect against<br />

false alarms from E.M.I. and R.F.I. Unit shall contain a red LED which shall pulse to indicate<br />

power on and which shall glow continuously to indicate alarm. Detector shall have a<br />

magnetically operated functional test switch and be capable of being supplied with a remote<br />

alarm LED indicator. Unit shall have a separate mounting base with terminal strip for ease of<br />

wiring, changing and cleaning.<br />

4. Duct Smoke Detectors: Locate type DH100 series photoelectric duct smoke detector. Duct<br />

housing base assembly shall be provided with an auxiliary relay with Form C contacts, rated<br />

at 1 AMP. Necessary sampling tubes shall be provided across the entire width of duct work.<br />

Those Duct Smoke Detectors installed above ceiling or not visible from viewing area shall be<br />

furnished with a remote test station type RTS-451KEY with a red light emitting diode (LED)<br />

mounted on a single gang stainless steel plate.<br />

5. Sprinkler Waterflow Switch: Shall be furnished and installed under Division 15 of the<br />

Specification and wired under this Section of the Specification. Switch shall have two (2) sets<br />

of N.O. contacts and adjustable retard chamber to compensate for water surge.<br />

6. Sprinkler System Gate Valve Supervisory Switch: Shall be furnished and installed under<br />

Division 15 of the Specification and wired under this Section of the Specification.<br />

J. ALARM INDICATING DEVICES<br />

Locate, where shown on the drawings, the following audio/visual devices:<br />

1. Audio/Visual Device shall be FireLite type P2R series (rectangular style), semi-flush on a<br />

standard electrical outlet box. A common mounting bezel shall contain the horn and high<br />

intensity xenon strobe flashing light. The side viewing white translucent lens shall have the<br />

word "FIRE" in red imprinted on it. Flash rate shall be 1 flash per second with an 15/75<br />

candela flash intensity or as marked on drawing. Both audio and visual units shall be on the<br />

same supervised circuit or circuits. The horn shall be rated at 87 db sound pressure level at<br />

ten (10) feet. Device shall be U.L. 1971 listed. All audio/visual units will include a<br />

synchronized flash module. All power supplies will be sized to appropriately account for<br />