Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 16140<br />

WIRING DEVICES<br />

PART 1 GENERAL<br />

1.01 SECTION INCLUDES<br />

A. Wall switches.<br />

B. Wall dimmers.<br />

C. Receptacles.<br />

D. Device plates and box covers.<br />

1.02 QUALITY ASSURANCE<br />

A. Conform to requirements of NFPA 70.<br />

B. Products: Provide products listed and classified by Underwriters Laboratories, Inc. as suitable for<br />

the purpose specified and indicated.<br />

PART 2 PRODUCTS<br />

2.01 WALL SWITCHES<br />

A. Wiring devices shall be of specification grade and the manufactured products of Hubbell, Pass<br />

and Seymour, Leviton, Eagle or Slater. Each receptacle shall be constructed to include a<br />

grounding pole from which a wired connection to ground shall be provided.<br />

B. Switches shall be as follows:<br />

1. Single pole- Hubbell 1221-I<br />

2. Two pole - Hubbell 1222-I<br />

3. Three way - Hubbell 1223-I<br />

C. Toggle switches shall be rated 20 ampere, 120-277 volts, except where otherwise shown on the<br />

drawings.<br />

D. Duplex receptacles<br />

1. Standard - Hubbell 5362-I<br />

2. Isolated Ground - Hubbell IG2162 (Orange)<br />

3. Ground Fault Interrupter - Hubbell GF5362I<br />

Leviton, Seymour, Slater, or Eagle will be considered as approved equals.<br />

E. Exterior weatherproof outlets<br />

1. Grade level (not installed on rooftops for service rooftop mechanical equipment)<br />

weatherproof outlets will be ground fault interrupter outlets mounted in weatherproof box<br />

and cover as manufactured by Pass & Seymour #4600 weatherproof heavy cast<br />

Aluminum Cover with #4600-26 enclosure with mounting plate tor GFCI outlet. All<br />

enclosures shall be keyed alike.<br />

2. Rooftop level weatherproof outlets will be ground fault interrupter outlets mounted in a<br />

weatherproof box and cover.<br />

F. Provide plates for all outlets, with opening configuration suitable for devices to be covered.<br />

Plates shall be in place with screws finished to match the plates. Plates will be brushed stainless<br />

steel.<br />

G. All plates used for motor starting switches shall be with engraving denoting its function.<br />

H. Covers for "FS" or "FD" boxes shall be corrosion resistant.<br />

PART 3 EXECUTION<br />

3.01 INSTALLATION<br />

A. Install in accordance with NECA "Standard of Installation."<br />

B. Install devices plumb and level.<br />