10.03.2015 Views

Specs

Specs

Specs

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

i. The activation of any standpipe or sprinkler valve tamper switch shall activate the system<br />

supervisory service audible signal and illuminate the LED at the control panel and the remote<br />

annunciator. Differentiation between valve tamper activation and opens and/or grounds on<br />

fire alarm initiation circuit wiring shall be provided.<br />

j. A combination waterflow indicator/sprinkler supervisory switch combination IDC type shall be<br />

selected allowing a single pair of wires to monitor both conditions. Waterflow monitor shall<br />

have priority over sprinkler supervisory monitoring.<br />

k. Activating the Supervisory Service Acknowledge Switch shall silence the supervisory audible<br />

signal while maintaining the Supervisory Service LED on indication that the tamper contact is<br />

still in the off-normal state.<br />

l. Restoring the valve to the normal position shall cause the Supervisory Service LED to<br />

extinguish, indicating restoration to normal.<br />

m. A manual evacuation means shall be provided to activate the system NACs.<br />

n. Alarm and trouble conditions shall be immediately displayed on the control panel front<br />

alphanumeric display. If more alarms or troubles are in the system, the operator shall be able<br />

to manually scroll to display new alarms. The first 10 fire alarm zones in alarm shall be<br />

displayed simultaneously in chronological order.<br />

o. The system shall have an alarm list means that shall allow the operator to display all alarms,<br />

troubles, and supervisory service conditions with the time of occurrence. This shall allow for<br />

the determination of the most recent alarm and may also indicate the path that the fire is<br />

taking.<br />

p. The control panel shall be capable of supplying 4 Amps @ 24 VDC power output for external<br />

system use including power for NACs.<br />

q. An additional internally mounted power supply rated at 5 Amps @ 24 VDC shall be provided.<br />

as required to service initiating circuits.<br />

19. SUPERVISION<br />

a. The system shall contain the number of independently supervised initiation circuits shown on<br />

the drawing plus a minimum of two spare circuits so that a fault in any one zone shall not<br />

affect any other zone. The alarm activation of any initiation circuit shall not prevent the<br />

subsequent alarm operation of any other initiation circuit.<br />

b. There shall be sprinkler supervisory initiation device circuits for connection of all sprinkler<br />

valve tamper switches to perform the Supervisory Service Operation. This independent<br />

initiation circuit shall be labeled Supervisory Service and shall differentiate between tamper<br />

switch activation and wiring faults.<br />

c. There shall be sufficient (number as required) independently supervised and independently<br />

fused NACs for audible notification appliances horns, and visible notification appliances.<br />

Disarrangement conditions of any circuit shall not affect the operation of other circuits.<br />

d. Each independently supervised circuit shall include a discrete panel readout to indicate<br />

disarrangement conditions per circuit.<br />

e. The incoming power to the system shall be supervised so that any power failure must be<br />

audibly and visibly indicated at the control panel and the remote annunciator. A green "power<br />

on" LED shall be displayed continuously while incoming power is present.<br />

f. The system batteries shall be supervised so that a low battery condition or disconnection of<br />

the battery shall be audibly and visibly indicated at the control panel and the remote<br />

annunciator.<br />

g. Additional monitoring shall be provided to initiate a depleted battery warning at the panel<br />

when battery operation has exceeded the battery capacity.<br />

h. The System Expansion Modules shall be electrically supervised for module placement.<br />

Should a module become disconnected from the controls, the system trouble indicator must<br />

illuminate and audible trouble signal must sound.<br />

i. The system shall have provisions for disabling and enabling all circuits individually for<br />

maintenance or testing purposes. Restoration of a disabled circuit displays the status of the<br />

circuit and initiates a count down timer allowing the operator to “Abort the Enable” to prevent<br />

unwanted activation of notification appliances, off-premise reporting, and emergency controls.<br />

FIRE ALARM (SCSS REV #3 4-1-10) 17000 - Page 5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!