Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 16060<br />

GROUNDING AND BONDING<br />

PART 1 GENERAL<br />

1.01 SECTION INCLUDES<br />

A. Grounding and bonding systems and requirements.<br />

1.02 PERFORMANCE REQUIREMENTS<br />

Grounding System Resistance: 5 ohms or less.<br />

PART 2 PRODUCTS<br />

2.01 CONNECTORS AND ACCESSORIES<br />

A. Provide electrical grounding conductors that are sized according to the NEC.<br />

B. Provide grounding and bonding products which are UL-Listed and labeled for their intended use.<br />

PART 3 EXECUTION<br />

3.01 INSTALLATION<br />

A. Install electrical grounding and bonding systems as indicated, in accordance with manufacturer’s<br />

instructions and applicable portions of NEC, NECA’s “Standard of Installation”, and in accordance<br />

with recognized industry practices to ensure compliance with requirements.<br />

B. Coordinate with other electrical work as necessary to interface installation of electrical grounding<br />

and bonding system with other work.<br />

C. Comply with applicable electrical code requirements of the authority having jurisdiction and<br />

NEC as applicable to electrical grounding and bonding, pertaining to systems, circuits and<br />

equipment.<br />

3.02 FIELD QUALITY CONTROL<br />

A. Inspect and test in accordance with NETA STD ATS except Section 4.<br />

B. Perform inspections and tests listed in NETA STD ATS, Section 7.13.<br />

END OF SECTION<br />

GROUNDING AND BONDING 16060 - Page 1 of 1