D. Belt-Driven Units: Motor mounted on adjustable base, with adjustable sheaves, enclosure<br />

around belts within fan housing, and lubricating tubes from fan bearings extended to outside of<br />

fan housing.<br />

E. Fan Wheels: Aluminum, airfoil blades welded to aluminum hub.<br />

F. Accessories: See Construction Documents.<br />

G. Capacities and Characteristics: See Construction Documents.<br />

2.2 PROPELLER FANS<br />

A. Basis-of-Design Product: Subject to compliance with requirements, provide Loren Cook Co. or<br />

comparable product by one of the following:<br />

1. Greenheck Fan Corp.<br />

2. PennBarry.<br />

B. Housing: Galvanized-steel sheet with flanged edges and integral orifice ring with primed finish<br />

coat applied after assembly for field painting and to match wall.<br />

C. Fan Wheel: Replaceable, extruded-aluminum, airfoil blades fastened to cast-aluminum hub;<br />

factory set pitch angle of blades.<br />

D. Fan Drive: Motor mounted in airstream, factory wired to disconnect switch located on outside of<br />

fan housing.<br />

E. Fan Drive:<br />

1. Shaft Bearings: Permanently lubricated, permanently sealed, self-aligning ball bearings.<br />

F. Accessories: See Construction Documents.<br />

G. Capacities and Characteristics: See Construction Documents.<br />

PART 3 - EXECUTION<br />

3.1 INSTALLATION<br />

A. Install power ventilators level and plumb.<br />

B. Support units per manufacturer’s installation instructions. Unit shall be level and plumb and on<br />

factory provided vibration isolators.<br />

C. Support suspended units from structure using threaded steel rods per manufacturer’s<br />

instructions.<br />

D. Install units with clearances for service and maintenance per manufacturer’s instructions.<br />

E. Label units according to requirements specified in Section 15077 "Identification for HVAC Piping<br />

and Equipment."<br />