Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

3.04 REINFORCEMENT AND ANCHORAGE - MASONRY VENEER<br />

A. Masonry Back-Up: Embed anchors in masonry back-up to bond veneer at maximum 2.0 sq ft of wall<br />

surface per anchor. Place additional anchors at perimeter of openings and ends of panels, so maximum<br />

spacing of anchors is 16 on center.<br />

3.05 LINTELS<br />

A. Install loose steel lintels over openings.<br />

3.06 CONTROL AND EXPANSION JOINTS<br />

A. Do not continue horizontal joint reinforcement through control and expansion joints.<br />

3.07 AIR MOISTURE BARRIER<br />

A. Install liquid applied air/moisture barrier on CMU wall. Product installation may be either spray or brush<br />

applied, per manufacturer’s installation procedures.<br />

B. Provide vapor retarder complying with this Section, for stud wall application.<br />

C. Install flashing as follows, unless otherwise indicated:<br />

1. Prepare masonry surfaces so they are smooth and free from projections that could puncture<br />

flashing. Where flashing is within mortar joint, place through-wall flashing on sloping bed of<br />

mortar and cover with mortar. Before covering with mortar, seal penetrations in flashing with<br />

adhesive, sealant, or tape as recommended by flashing manufacturer.<br />

2. At lintels and shelf angles, extend flashing a minimum of 6 inches into masonry at each end. At<br />

heads and sills, extend flashing 6 inches at ends and turn up not less than 2 inches to form end<br />

dams.<br />

3. Install metal drip edges beneath flexible flashing at exterior face of wall. Stop flexible flashing ½<br />

inch back from outside face of wall and adhere flexible flashing to top of metal drip edge.<br />

3.08 TOLERANCES<br />

A. Maximum Variation From Unit to Adjacent Unit: 1/16 inch.<br />

B. Maximum Variation from Plane of Wall: 1/4 inch in 10 ft.<br />

C. Maximum Variation from Plumb: 1/4 inch per story non-cumulative.<br />

D. Maximum Variation from Level Coursing: 1/8 inch in 3 ft and 1/4 inch in 10 ft..<br />

END OF SECTION<br />

MASONRY VENEER 04816 - Page 3 of 3