Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

3. Hydraulic Calculations: The calculated demand including hose stream requirements shall fall<br />

no less than 10 percent below the available supply curve.<br />

4. Water Supply:<br />

a. Elevation of static and elevation of residual test gage: 600 mm (2 ft.) above site grade<br />

b. Static pressure: _____ kPa (psi)<br />

c. Residual pressure: _____ kPa (psi)<br />

d. Flow: _____ L/s (gpm)<br />

e. Date:_____ Time:______<br />

C. For each sprinkler zone provide a control valve, flow switch, self-contained test and drain<br />

assembly and pressure gage.<br />

D. Provide a guard for each sprinkler in the janitor’s closets, and sprinklers within 2100 mm (7 ft.) of<br />

the floor and other areas as required by NFPA 13.<br />

E. Seismic Protection: Seismically brace all new and existing piping systems in accordance with<br />

Zone _____ of NFPA 13.<br />

1.5 CONTRACTORS QUALIFICATIONS:<br />

A. Design and installation of this project shall be accomplished by a contractor who meets the<br />

following qualifications:<br />

1. Engages on a regular and full time basis in the design and installation of automatic sprinkler<br />

systems.<br />

2. Employ or contract on a regular basis for system design, a professional engineer or at least<br />

one person having passed the elements for a NICET Level III rating in automatic sprinkler<br />

design.<br />

3. Can provide on-site emergency service within four hours notification.<br />

1.6 SUBMITTALS<br />

A. Submit as one package in accordance with Section 01340 SAMPLES AND SHOP DRAWINGS.<br />

B. Sprinkler design professional’s Registration or Certification.<br />

C. Emergency service point of contact name and 24 hour emergency telephone number.<br />

D. Manufacturer’s Literature and Data:<br />

1. Pipe and fittings.<br />

2. Valves<br />

3. Drips<br />

4. Fire Department Siamese Connection<br />

5. Sprinklers-each type and model<br />

6. Air Compressors<br />

7. Inspectors Test Alarm Modules<br />

8. Sprinkler Cabinets<br />

9. Sprinkler Plugs<br />

DRY PIPE AUTOMATIC SPRINKLER FIRE PROTECTION 15500 - Page 2 of 10