Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

j. The count down timer shall be programmable from the front panel to be from 0 to 60 minutes.<br />

C. POWER REQUIREMENTS<br />

1. The control panel shall receive power as noted on the plans via a dedicated 20A, 120vac, fused<br />

disconnect circuit.<br />

2. The system shall be provided with sufficient battery capacity to operate the entire system upon<br />

loss of normal AC mains power in a normal supervisory mode for a period of sixty (60) hours with<br />

5 minutes of alarm operation at the end of this period. The system shall automatically transfer to<br />

the standby batteries upon power failure. All battery charging and recharging operations shall be<br />

automatic.<br />

3. All circuits requiring system operating power shall be 24 VDC and shall be individually fused at<br />

the control panel.<br />

D. SUBMITTALS<br />

1. Submit Manufacturer product data sheets for all proposed devices and equipment.<br />

2. Provide wiring diagrams, equipment ratings, dimensions, and finishes for all proposed devices<br />

and equipment.<br />

3. If submittals, upon review by the Owner and/or the Owners Representative, are found not to<br />

conform with the performance, type and quality of products as well as all other requirements of<br />

these specifications; the Contractor shall be required to resubmit. The Contractor shall be<br />

responsible for the Owner's extra expenses for subsequent review(s) of rejected submittals. Such<br />

extra fees shall be deducted from payments by the Owner to the Contractor. Approval of the<br />

submittals by the Owner shall, in no case, relieve the Contractor of the responsibility to meet the<br />

requirements of this specification.<br />

E. PROJECT RECORD (AS-BUILT) DRAWINGS<br />

1. The National Account Vendor shall provide and maintain on the site an up-to-date record set<br />

of approved shop drawings.<br />

2. Record drawings shall include location of end-of-line device locations.<br />

3. Upon completion of the work, and final acceptance by the local authority, the Contractor shall<br />

submit record drawings to the Owner and the Engineer.<br />

F. OPERATION AND MAINTENANCE DATA<br />

1. Submit Manufacturer data sheets for all equipment installed.<br />

2. Include operating, installation, and routine maintenance instructions.<br />

3. Include Manufacturer letter stating the date of installation on which the system is operational.<br />

G. SUBSTITUTIONS<br />

1. Other equipment may be substituted as long as the level of quality and performance of<br />

operation is equal to, or greater than, that which is specified. The Owner and/or Owners<br />

Representative shall make the determination as to whether or not the substitute<br />

equipment is acceptable.<br />

H. FIRE DETECTION AND CONTROL PANEL<br />

1. Where shown on the plans, locate a Firelite type MS-10UD Fire Alarm Control Panel.<br />

Construction shall be modular with solid state, microprocessor based electronics.<br />

2. A local audible device shall sound during Alarm, Trouble or Supervisory conditions. This<br />

audible device shall pulse to indicate alarm conditions and shall be on steadily for<br />

Supervisory or Trouble conditions.<br />

3. Primary Keys & Panel Display<br />

a. The Control Panel’s display shall be backlit for enhanced readability. So as to conserve<br />

battery standby power, it shall not be lit during an AC power failure unless an alarm<br />

condition occurs or there should be keypad activity.<br />

b. The display shall support both upper and lower case letters. Lowercase letters shall be<br />

used for softkey titles and prompting the user. Uppercase letters shall be used for System<br />

Status Information. A cursor shall be visible when entering information.<br />

4. The fire alarm control panel cabinet shall provide the following features:<br />

a. The fire alarm control panel shall be housed in a single cabinet capable of housing the<br />

maximum of expansion and optional modules required for system feature upgrading or<br />

system expansion.<br />

FIRE ALARM (SCSS REV #3 4-1-10) 17000 - Page 6