10.03.2015 Views

Specs

Specs

Specs

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

d. Wiring for 24 volt DC control, alarm notification, emergency communication and similar<br />

power-limited auxiliary functions may be run in the same conduit as initiating and<br />

signaling line circuits.<br />

e. Conduit shall not enter the fire alarm control panel, or any other remotely mounted control<br />

panel equipment or backboxes, except where conduit entry is specified by the FACP<br />

manufacturer.<br />

f. Contractor shall be responsible for satisfying all conduit fill requirements. Conduit cross<br />

sectional conductor fill shall not exceed 40% under any circumstances.<br />

2. Wire:<br />

a. All fire alarm system wiring as installed under this contract shall be new “Fire Wire” from<br />

FACP to device.<br />

b. Wiring shall be in accordance with local, state and national codes (e.g., NEC Article 760)<br />

and as recommended by the manufacturer of the fire alarm system. Number and size of<br />

conductors shall be as recommended by the fire alarm system manufacturer, but not less<br />

than 16 AWG for initiating device circuits and signaling line circuits, and 14 AWG for<br />

notification appliance circuits.<br />

c. All wire and cable shall be listed and/or approved by a recognized testing agency for use<br />

with a protective signaling system.<br />

d. All field wiring shall be completely supervised.<br />

3. Terminal Boxes, Junction Boxes and Cabinets:<br />

All boxes and cabinets shall be UL listed for their use and purpose. All junction boxes shall<br />

be painted red.<br />

4. Initiating circuits shall be arranged to serve like categories (manual, smoke, waterflow). Mixed<br />

category circuitry shall not be permitted except on signaling line circuits connected to<br />

intelligent reporting device.<br />

P. INSTALLATION<br />

1. Installation of equipment and final devices that pertain to other work in the contract shall be<br />

closely coordinated with the appropriate Subcontractors.<br />

2. The contractor shall clean all dirt and debris from the inside and the outside of the fire alarm<br />

equipment after completion of the installation.<br />

3. All junction boxes shall be sprayed red and/or labeled "Fire Alarm". Wiring color code shall be<br />

maintained throughout the installation.<br />

4. Provide and install the system in accordance with the plans and specifications, all applicable<br />

codes, and the Manufacturer's recommendations. All wiring shall be installed in accordance<br />

with all applicable codes and standards. Upon completion of installation, the Contractor shall<br />

so certify, in writing, to the Owner and the General Contractor.<br />

S. FIRE ALARM WIRING<br />

1. All wiring shall be color coded as follows and must be installed within conduit:<br />

a. Fire alarm control panel - 120 Volt - 2 #12 AWG.<br />

b. Alarm initiating devices - 2 #16 AWG per zone, one (1) brown, on (1) violet.<br />

c. Horn devices - 2 #14 AWG per circuit. One (1) red, one (1) black.<br />

d. Visual devices - on same circuit as horn devices.<br />

e. Slave fan relay - 2 #14 AWG blue wires from fire alarm control panel to fan relay.<br />

f. Magnetic door holder device - 2 #14 AWG yellow wires from fire alarm control panel to<br />

holders.<br />

g. Remote annunciator/graphic device - 2 #14 and 1 pair #18 AWG. All wires #14 AWG and<br />

properly identified at control panel and annunciator locations.<br />

2. Install and connect conduit and wiring from fire alarm control panel to telephone terminal<br />

cabinet for central station tie.<br />

3. All junction boxes used with the fire alarm system will be painted red.<br />

4. Coordinate connections with supplies of central station network system.<br />

END OF SECTION<br />

FIRE ALARM (rev 2 2-11-10) 16721 - Page 2 of 2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!