Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

b. The controller shall have a clock to operate the exhaust fan equipment on<br />

a time basis, without high CO concentration. The fans shall operate from<br />

zero to eight minutes (field adjustable in on minute increments) per hour.<br />

This timed fan run shall be different from the minimum run time setting. A<br />

switch shall be provided to enable to disable the time base operation<br />

c. The CO controller shall be designed such that in the event of a power<br />

failure the control unit shall set itself to an alarm condition and upon<br />

power restoration shall automatically activate the fan output to clear any<br />

possible accumulated toxic gases.<br />

d. The controller shall have an LED to indicate alarm condition of the<br />

remote sensor.<br />

e. Options available for CO System Controllers:<br />

1. Power "ON" light emitting diode (LED) to indicate power to system<br />

2. Fan ON (LED) indication<br />

3. Local alarm horn and/or light. Horn has silence switch.<br />

4. Remote alarm panel.<br />

5. Calibration Kit.<br />

6. Keyed panel lock(s.)<br />

B. Design Requirements:<br />

1. Provide clearly labeled light emitting diodes (LED’s) indicating lamps on the face<br />

of the controller panel to indicate the following:<br />

a. Power "ON" to system -- Green LED.<br />

b. One Red LED to indicate high CO condition (warning level).<br />

c. One Red LED to indicate Alarm condition.<br />

2. Provide an audible alarm with a minimum sound intensity of 68dB, on the face of<br />

the control panel. Provide an "Audible Silence" push button switch to silence the<br />

audible. Audible silence circuit shall be self resetting so that after alarm is<br />

cleared the audible alarm will automatically resound on the next alarm<br />

activation.<br />

3. Provide a Green LED on the face of the control panel to prove, when lighted, that<br />

the remote Sensor has power.<br />

4. Provide a remote CO alarm panel and mount where indicated on the plans. The<br />

remote alarm panel shall include a red LED alarm lamp and an audible alarm,<br />

with a minimum sound intensity of 68dB. Provide an "Audible Silence"<br />

momentary push button switch to silence the audible. The alarm LED must stay<br />

lighted as long as the alarm condition persists.<br />

C. Performance Requirements:<br />

1. Automatic fan run upon power restoration<br />

2. Input Power: 120VAC, 60Hz, 1A (fused)<br />

3. Relay Contacts: 24VAC, 2A resistive, 1.5A inductive<br />

4. Timers: 30 second delay on<br />

a. Min. Fan Run Time 1-8 minutes<br />

b. Hourly Fan Run 0-8 minutes<br />

5. Enclosure:<br />

GAS DETECTION AND ALARM 13850- PAGE 2 OF 5