Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 17000<br />

SPRINKLER SUPERVISORY, FIRE ALARM & MONITORING SYSTEM<br />

PART 1 GENERAL<br />

1.01 FIRE ALARM SYSTEM<br />

A. SCOPE & RELATED DOCUMENTS<br />

1. National Account Vendor as listed on drawings shall furnish and install a complete Fire Alarm<br />

System as described herein and as shown on the plans; to be wired, connected, and left in first<br />

class operating condition. The system shall use closed loop initiating device circuits with<br />

individual zone supervision, individual NAC supervision, incoming and standby power<br />

supervision. Include a control panel, manual stations (fire alarm boxes), automatic fire detectors,<br />

indicating devices, remote enunciators, all wiring, connections to devices, outlet boxes, junction<br />

boxes, and all other necessary material for a complete operating system.<br />

2. The work covered by this section of the specifications includes the furnishing of all labor,<br />

drawings, equipment, materials, and performance of all operations in connection with the<br />

installation of the Fire Alarm System as shown on the drawings and as herein specified.<br />

3. The requirements of the conditions of the Contract, Supplementary Conditions and General<br />

Requirements, apply to the work specified in this section.<br />

4. The complete installation is to conform to the applicable sections of NFPA-72, Local Code<br />

Requirements and National Electrical Code with particular attention to Article 760.<br />

5. Additionally, the entire installed system and all integrated system operations shall be within the<br />

guidelines of the Basic Building Code.<br />

6. The work covered by this section of the specifications is to be coordinated with the related work<br />

as specified elsewhere under the project specifications.<br />

7. The approved vendor is a National Account Vendor as listed on drawings as designated on<br />

drawings. No substitutions allowed.<br />

8. Knox Box shall be provided by the General Contractor with tamper switch and wired by the<br />

National Account as designated on drawings for tamper monitoring. Supervisory signal to be sent<br />

to the National Account as designated on drawings Net Center for 24 hr. Remote Station<br />

Monitoring.<br />

9. Remote Station monitoring of the fire alarm system shall be provided by the National Account as<br />

designated on drawings under separate contract with the owner. Any other local requirements for<br />

signals to be sent to the location fire department directly shall be by the owner.<br />

B. REFERENCES<br />

NFPA 72, the National Fire Alarm Code<br />

NFPA 101 - Life Safety Code®<br />

Building Code appropriate for this Jurisdiction.<br />

Other Applicable Codes and/or Standards<br />

C. REGULATORY REQUIREMENTS<br />

1. Equipment: All devices, combinations of devices, notification appliances, and equipment, shall be<br />

listed for the protective signaling purpose for which they are used and shall be installed in<br />

compliance with applicable codes and standards.<br />

2. Type of System: The control panel shall be Listed for power-limited applications per NEC 760 and<br />

for compliance with the National Fire Protection Association Standards NFPA 72; for Local,<br />

Auxiliary, Remote Station, and/or Proprietary fire protective signaling systems.<br />

3. Type of Service: The control panel shall be Listed for the applicable types of service, i.e.; Manual<br />

Alarm, Automatic Alarm, Waterflow Alarm and/or Sprinkler Supervisory Service.<br />

4. Type of Signaling: The control panel shall be Listed for the applicable types of signaling methods<br />

used, i.e.; Temporal Coded, Zone Coded, Non-Coded, June Time and/or Digital Alarm<br />

Communicator (DACT) Signaling.<br />

FIRE ALARM (SCSS REV #3 4-1-10) 17000 - Page 1