so certify, in writing, to the Owner and the General Contractor.<br />

N. FIELD QUALITY CONTROL<br />

1. The completed fire alarm system shall be fully tested in accordance with NFPA-72, Chapter<br />

7, [and local Fire Department requirements,] by the Installer, in the presence of the Owner's<br />

representative and the Local Fire Marshal. Upon completion of a successful test, the Installer<br />

shall so certify, in writing, to the Owner and General Contractor.<br />

2. The Manufacturer shall provide on-site technical installation support.<br />

O. MANUFACTURER'S FIELD SERVICES<br />

1. Include on-site services of a National Account certified technician to provide technical<br />

installation support for panel start up, program editing, troubleshooting of the Fire Protective<br />

Signaling System Control Panel, and assistance to the Installer for one complete final system<br />

checkout in accordance with the Field Quality Control section of these specifications. The<br />

Manufacturer shall also provide one training session with the Owner, or Owners<br />

Representatives, upon completion of installation, for instruction of system operation.<br />

P. FIRE ALARM WIRING<br />

1. All wiring shall be color coded as follows and must be installed within conduit:<br />

a. Fire alarm control panel - 120 Volt - 2 #12 AWG.<br />

b. Alarm initiating devices - 2 #14 AWG per zone, one (1) brown, on (1) violet.<br />

c. Horn devices - 2 #16 AWG per circuit. One (1) red, one (1) black.<br />

d. Visual devices - on same circuit as horn devices.<br />

e. Slave fan relay - 2 #14 AWG blue wires from fire alarm control panel to fan relay.<br />

f. Magnetic door holder device - 2 #14 AWG yellow wires from fire alarm control panel to<br />

holders.<br />

g. Remote annunciator/graphic device - 2 #14 and 1 pair #18 AWG. All wires #14 AWG and<br />

properly identified at control panel and annunciator locations.<br />

2. Install and connect conduit and wiring from fire alarm control panel to telephone terminal<br />

cabinet for central station tie.<br />

3. All junction boxes used with the fire alarm system will be painted red.<br />

4. Coordinate connections with supplies of central station network system.<br />

END OF SECTION<br />