Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 16131<br />

CONDUIT<br />

PART 1 GENERAL<br />

1.01 SECTION INCLUDES<br />

A. Conduit, fittings and conduit bodies.<br />

1.02 QUALITY ASSURANCE<br />

A. Conform to requirements of NFPA 70.<br />

B. Products: Listed and classified by Underwriters Laboratories, Inc. as suitable for purpose specified<br />

and shown.<br />

PART 2 PRODUCTS<br />

2.01 CONDUIT REQUIREMENTS<br />

A. All conduit shall be EMT, except for exterior or hazardous area. All conduits routed in exterior or<br />

hazardous area, shall be heavy wall (rigid) galvanized steel type with threaded type fittings. All<br />

conduit shall be as manufactured by International Tube Company or equal.<br />

B. All conduit fitting shall conform to all applicable codes.<br />

C. PVC Schedule 40 shall only be permitted below grade of building exterior footprint; conduit shall<br />

transition to GRS where exposed.<br />

PART 3 EXECUTION<br />

3.01 EXAMINATION<br />

A. Verify that field measurements are as shown on drawings.<br />

B. Verify routing and termination locations of conduit prior to rough-in.<br />

C. Conduit routing is shown on drawings in approximate locations unless dimensioned. Route as<br />

required to complete wiring system.<br />

3.02 INSTALLATION<br />

A. Install conduit in accordance with NECA Standard of Installation.<br />

B. Install nonmetallic conduit in accordance with manufacturer's instructions.<br />

C. Arrange conduit to maintain headroom and present neat appearance.<br />

D. Route exposed conduit parallel and perpendicular to walls.<br />

E. Install no more than equivalent of three 90 degree bends between boxes. Use conduit bodies to<br />

make sharp changes in direction, as around beams. Use hydraulic one shot bender to fabricate<br />

bends in metal conduit larger than 2 inch size.<br />

F. Avoid moisture traps; provide junction box with drain fitting at low points in conduit system.<br />

G. All conduit to be supported either from joist or ceiling, as directed by the drawings.<br />

3.03 INTERFACE WITH OTHER PRODUCTS<br />

A. Install conduit to preserve fire resistance rating of partitions and other elements.<br />

B. Route conduit through roof openings for piping and duct work wherever possible.<br />

END OF SECTION<br />