e. Conduit shall not enter the security alarm control panel, or any other remotely mounted<br />

control panel equipment or backboxes, except where conduit entry is specified by the<br />

manufacturer.<br />

f. Contractor shall be responsible for satisfying all conduit fill requirements. Conduit cross<br />

sectional conductor fill shall not exceed 40% under any circumstances.<br />

2. Wire:<br />

a. All security alarm system wiring as installed under this contract shall be new “BA Wire”<br />

from the control panel to device.<br />

b. Wiring shall be in accordance with local, state and national codes (e.g., NEC Article 760)<br />

and as recommended by the manufacturer of the fire alarm system. Number and size of<br />

conductors shall be as recommended by the alarm system manufacturer, but not less<br />

than 18 AWG for initiating device circuits and signaling line circuits, and 14 AWG for<br />

notification appliance circuits.<br />

c. All wire and cable shall be listed and/or approved by a recognized testing agency for use<br />

with a protective signaling system.<br />

d. All field wiring shall be completely supervised.<br />

3. Terminal Boxes, Junction Boxes and Cabinets:<br />

All boxes and cabinets shall be UL listed for their use and purpose. l<br />

4. Initiating circuits shall be arranged as shown on drawing E-8 to serve like categories (motion<br />

sensors, door contacts). Mixed category circuitry shall not be permitted except on signaling<br />

line circuits connected to intelligent reporting device.<br />

P. INSTALLATION<br />

1. Installation of equipment and final devices that pertain to other work in the contract shall be<br />

closely coordinated with the appropriate Subcontractors.<br />

2. The contractor shall clean all dirt and debris from the inside and the outside of the fire alarm<br />

equipment after completion of the installation.<br />

3. Provide and install the system in accordance with the plans and specifications, all applicable<br />

codes, and the Manufacturer's recommendations. All wiring shall be installed in accordance<br />

with all applicable codes and standards. Upon completion of installation, the Contractor shall<br />

so certify, in writing, to the Owner and the General Contractor.<br />

S. SECURITY ALARM WIRING<br />

1. All wiring shall be color coded as follows and must be installed within conduit:<br />

a. Security alarm control panel – plug-in transformer to panel - 2 #16 AWG cable.<br />

b. Alarm initiating devices - 4 #18 AWG, white jacketed cable per zone,<br />

g. Remote annunciator/graphic device – 2pair #16, twisted/shielded cable. Cable shall be<br />

properly identified at control panel and annunciator locations.<br />

2. Install and connect conduit and wiring from security alarm control panel to telephone terminal<br />

cabinet for central station tie.<br />

3. Coordinate connections with supplies of central station network system.<br />

END OF SECTION<br />