Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: March 2011a<br />

C. Install switches with OFF position down.<br />

D. Install wall dimmers to achieve full rating specified and indicated after derating for ganging as<br />

instructed by manufacturer.<br />

E. Do not share neutral conductor on load side of dimmers.<br />

F. Install receptacles with grounding pole on top.<br />

G. Connect wiring device grounding terminal to outlet box with bonding jumper.<br />

H. Install decorative plates on switch, receptacle, and blank outlets in finished areas.<br />

I. Connect wiring devices by wrapping conductor around screw terminal.<br />

J. Use jumbo size plates for outlets installed in masonry walls.<br />

K. Install galvanized steel plates on outlet boxes and junction boxes in unfinished areas, above<br />

accessible ceilings, and on surface mounted outlets.<br />

L. Install protective rings on active flush cover service fittings.<br />

3.02 INTERFACE WITH OTHER PRODUCTS<br />

A. Coordinate locations of outlet boxes provided under Section 16138 to obtain mounting heights<br />

specified.<br />

B. Install wall switch 48 inches above finished floor.<br />

C. Install convenience receptacle 48 inches above finished floor in service area, 18 inches above<br />

finished floor in all other areas unless noted otherwise.<br />

D. Install convenience receptacle 6 inches above counter.<br />

E. Install dimmer 48 inches above finished floor.<br />

F. Install telephone jack 18 inches above finished floor.<br />

G. Install telephone jack for side-reach wall telephone to position top of telephone at 54 inches<br />

above finished floor.<br />

H. Install telephone jack for forward-reach wall telephone to position top of telephone at 48 inches<br />

above finished floor.<br />

3.03 FIELD QUALITY CONTROL<br />

A. Inspect each wiring device for defects.<br />

B. Operate each wall switch with circuit energized and verify proper operation.<br />

C. Verify that each receptacle device is energized.<br />

D. Test each receptacle device for proper polarity.<br />

E. Test each GFCI receptacle device for proper operation.<br />

3.04 ADJUSTING<br />

A. Adjust devices and wall plates to be flush and level.<br />

3.05 CLEANING<br />

A. Clean exposed surfaces to remove splatters and restore finish.<br />

END OF SECTION<br />

WIRING DEVICES 16140 - Page 2 of 2