Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 16722<br />

SECURITY ALARM – conduit only<br />

PART 1 GENERAL<br />

1.01 SECURITY ALARM SYSTEM<br />

A. SCOPE & RELATED DOCUMENTS<br />

1. Furnish and install conduit for the Security Alarm System as described herein and as shown<br />

on the plans; pull string shall be provided in the conduit by this contractor. Provide all outlet<br />

boxes, junction boxes, and all other necessary material for a complete installation.<br />

2. The Electrical Contractor shall provide conduit and wire for the 120vac power connection to<br />

the security alarm panel. Electrical Contractor to furnish and install all conduit for all the<br />

security alarm peripheral devices attached to the system. Electrical Contractor shall stub<br />

conduit up into the ceiling joist and leave a pull string in the conduit.<br />

3. The requirements of the conditions of the Contract, Supplementary Conditions and General<br />

Requirements, apply to the work specified in this section.<br />

4. The complete installation is to conform to the applicable sections of NFPA-72, Local Code<br />

Requirements and National Electrical Code with particular attention to Article 760.<br />

5. Additionally, the entire installed system and all integrated system operations shall be within<br />

the guidelines of the BOCA Basic Building Code.<br />

6. The work covered by this section of the specifications is to be coordinated with the related<br />

work as specified elsewhere under the project specifications.<br />

B. REFERENCES<br />

NFPA 72, the National Fire Alarm Code<br />

NFPA 101 - Life Safety Code®<br />

BOCA<br />

Other Applicable Codes and/or Standards<br />

1.02 CONDUIT AND WIRE<br />

A. POWER REQUIREMENTS<br />

1. The control panel shall receive 120VACpower as noted on the plans via an outlet mounted at<br />

the control panel for a plug-in transformer.<br />

2. 120vac power outlets are also required for the “Assistance Call System”, “Outside Parts<br />

Doors” and the Inventory Room electric door strikes. See E-8 for locations.<br />

3. All circuits requiring system operating power shall be 12 VDC and shall be individually fused<br />

at the control panel.<br />

O. CONDUIT AND WIRE:<br />

1. Conduit:<br />

a. Conduit shall be in accordance with The National Electrical Code (NEC), local and state<br />

requirements and as described elsewhere in this specification.<br />

b. All wiring shall be installed in conduit or approved metallic raceway. Conduit fill shall not<br />

exceed 40 percent of interior cross sectional area where three or more cables are<br />

contained within a single conduit.<br />

c. Cable must be separated from any open conductors of power, or Class 1 circuits, and<br />

shall not be placed in any conduit, junction box or raceway containing these conductors,<br />

per NEC Article 760-29.<br />

d. Wiring for 12 volt DC control, alarm notification, emergency communication and similar<br />

power-limited auxiliary functions may be run in the same conduit as initiating and<br />

signaling line circuits.<br />