Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

synchronized flash power consumption.<br />

2. Visual only units will be FireLite type SR series similar to as specified above.<br />

K. REMOTE DEVICES<br />

Locate, where shown on the drawings, the following remote devices:<br />

1. Slave Fan Relays: Furnish and install type MR-101/C/R fan relay with required contacts.<br />

Cabinet shall have a screw on cover. Minimum contact rating shall be 10 AMP resistive.<br />

L. CONDUIT AND WIRE: (PROVIDED BY THE ELECTRICAL CONTRACTOR)<br />

1. Conduit:<br />

a. Conduit shall be in accordance with The National Electrical Code (NEC), local and state<br />

requirements and as described elsewhere in specification 16721, and provided by the<br />

Electrical Contractor.<br />

b. All wiring shall be installed in conduit or approved metallic raceway. Conduit fill shall not<br />

exceed 40 percent of interior cross sectional area where three or more cables are<br />

contained within a single conduit.<br />

c. Cable must be separated from any open conductors of power, or Class 1 circuits, and<br />

shall not be placed in any conduit, junction box or raceway containing these conductors,<br />

per NEC Article 760-29.<br />

d. Wiring for 24 volt DC control, alarm notification, emergency communication and similar<br />

power-limited auxiliary functions may be run in the same conduit as initiating and<br />

signaling line circuits. All circuits shall be provided with transient suppression devices and<br />

the system shall be designed to permit simultaneous operation of all circuits without<br />

interference or loss of signals.<br />

e. Conduit shall not enter the fire alarm control panel, or any other remotely mounted control<br />

panel equipment or backboxes, except where conduit entry is specified by the FACP<br />

manufacturer.<br />

f. Contractor shall be responsible for satisfying all conduit fill requirements. Conduit cross<br />

sectional conductor fill shall not exceed 40% under any circumstances.<br />

2. Wire:<br />

a. All fire alarm system wiring as installed under this contract shall be new “Fire Wire” from<br />

FACP to device.<br />

b. Wiring shall be in accordance with local, state and national codes (e.g., NEC Article 760)<br />

and as recommended by the manufacturer of the fire alarm system. Number and size of<br />

conductors shall be as recommended by the fire alarm system manufacturer, but not less<br />

than 16 AWG for initiating device circuits and signaling line circuits, and 14 AWG for<br />

notification appliance circuits.<br />

c. All wire and cable shall be listed and/or approved by a recognized testing agency for use<br />

with a protective signaling system.<br />

d. All field wiring shall be completely supervised.<br />

3. Terminal Boxes, Junction Boxes and Cabinets:<br />

All boxes and cabinets shall be UL listed for their use and purpose. All junction boxes shall<br />

be painted red.<br />

4. Initiating circuits shall be arranged to serve like categories (manual, smoke, waterflow). Mixed<br />

category circuitry shall not be permitted except on signaling line circuits connected to<br />

intelligent reporting device.<br />

M. INSTALLATION<br />

1. Installation of equipment and devices that pertain to other work in the contract shall be<br />

closely coordinated with the appropriate Subcontractors.<br />

2. The security vendor shall clean all dirt and debris from the inside and the outside of the fire<br />

alarm equipment after completion of the installation.<br />

3. All junction boxes shall be sprayed red and/or labeled "Fire Alarm". Wiring color code shall be<br />

maintained throughout the installation.<br />

4. Install all system components in accordance with the plans and specifications, all applicable<br />

codes, and the Manufacturer's recommendations. All wiring shall be installed in accordance<br />

with all applicable codes and standards. Upon completion of installation, the Contractor shall<br />

FIRE ALARM (SCSS REV #3 4-1-10) 17000 - Page 8