SECTION 15000<br />

AUTOMATIC SPRINKLER SYSTEMS<br />

PART 1 - GENERAL<br />

1.01 GENERAL:<br />

A. The General Conditions, Division 101 of General Requirements, Section 15010 - Standard Provisions,<br />

and Section 15050 - Basic Material and Methods are hereby made a part of this section.<br />

1.02 SCOPE:<br />

A. Furnish all labor, materials, tools, equipment and related items required for the complete design and<br />

installation of Automatic Sprinkler System.<br />

B. All areas of the building shall be protected by wet Automatic Fire Sprinklers, except for the areas<br />

defined in Section 15500 “Dry Pipe Automatic Sprinkler Fire Protection”. The system shall be<br />

hydraulically calculated. Density shall be in accordance with NFPA-13 unless special circumstances<br />

such as stacking heights or materials to be stored cause other chapters of the NFPA to be required.<br />

Follow those chapters for the appropriate sprinklering requirements.<br />

C. Fire Sprinkler Contractor shall field verify all existing conditions prior to designing and installing system.<br />

D. Water supply shall come from a new fire line service complete with double check backflow preventer,<br />

and valving as required by the city. Fire sprinkler contractor shall pay all tap fees, permits, and charges<br />

necessary for a complete and approved installation.<br />

E. Preparation of detailed shop drawings for the fire protection systems to meet the approval of state and<br />

local authorities having jurisdiction on this project. FDC shall provide the seal and signature of a<br />

licensed professional engineer on the shop drawings and calculations at time of submittal.<br />

1.03 QUALITY ASSURANCE:<br />

A. Sprinkler System shall comply with all applicable State and City Codes, NFPA Requirements, and<br />

Owner's Insurance Company Requirements; including, but not limited to the following:<br />

1. Uniform Building Code.<br />

2. NFPA Chapter 13.<br />

3. Life Safety Code NFPA-101.<br />

4. Uniform Fire Code.<br />

1.04 SUBMITTALS:<br />

A. Prepare detailed working drawings of the Automatic Sprinkler System.<br />

B. Submit drawings and calculations to the Fire Marshal and Owner's Insurance Underwriter and obtain<br />

their approval.<br />

C. Submit four (4) copies of approved drawings and calculations to the Architect and two (2) copies to the<br />

Fire Marshal for their review and approval.<br />

D. Submit "cutsheet" samples of Sprinkler Heads to Architect for approval.<br />

PART 2 - PRODUCTS<br />

2.01 GENERAL:<br />

A. All materials, equipment, valves and devices installed or furnished under this contract shall be listed and<br />

approved for use by the authorities, agencies, codes and standards cited in this section of the<br />

specifications.<br />