Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 15146<br />

PLUMBING SPECIALTIES<br />

PART 1 GENERAL<br />

1.01 SECTION INCLUDES<br />

A. Floor drains.<br />

B. Cleanouts.<br />

C. Hose bibs.<br />

D. Trench Drains<br />

E. Backflow preventers.<br />

F. Thermostatic Mixing Valves.<br />

G. Trap Primers.<br />

PART 2 PRODUCTS<br />

2.01 DRAINS<br />

A. Floor Drains<br />

1. Manufacturers: Subject to compliance with requirements, provide product by one of the<br />

following.<br />

2. Basis-of-Design Product: J.R. Smith or comparable product by one of the following.<br />

a. Zurn<br />

3. ASME A112.21.1M; lacquered cast iron two piece body with double drainage flange, weep<br />

holes, reversible clamping collar, and round, adjustable nickel-bronze strainer.<br />

2.02 CLEANOUTS<br />

A. Cleanouts at Exterior Surfaced Areas (GCO):<br />

1. Manufacturer: Subject to compliance with requirements, provide product by one of the<br />

following.<br />

2. Basis-of-Design Product: J.R. Smith or comparable product by one of the following.<br />

a. Wade<br />

b. Zurn<br />

3. Round cast nickel bronze access frame and non-skid cover.<br />

B. Cleanouts at Interior Finished Floor Areas (FCO):<br />

1. Manufacturer: Subject to compliance with requirements, provide product by one of the<br />

following.<br />

2. Basis-of-Design Product: J.R. Smith or comparable product by one of the following.<br />

a. Wade<br />

b. Zurn<br />

3. Lacquered cast iron body with anchor flange, reversible clamping collar, threaded top<br />

assembly, and round gasketed scored cover in service areas and round gasketed depressed<br />

cover to accept floor finish in finished floor areas.<br />

C. Cleanouts at Interior Unfinished Accessible Areas SCO/WCO: Caulked or threaded type. Provide<br />

bolted stack cleanouts on vertical rainwater leaders.<br />

2.03 HOSE BIBBS, HYDRANTS, VALVES, AND WATER HAMMER ARRESTORS<br />

A. Interior Hose Bibbs:<br />

1. Manufacturer: Subject to compliance with requirements, provide product by one of the<br />

following.<br />

2. Basis-of-Design Product: Chicago Faucet or comparable product by one of the following.<br />

a. Watts<br />

b. Woodford<br />

PLUMBING SPECIALITIES 15146 - Page 1 of 3