Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

SECTION 13850<br />

GAS DETECTION AND ALARM<br />

PART 1 GENERAL<br />

1.01 SECTION INCLUDES<br />

A. Remote CO Sensors.<br />

B. CO System Controller.<br />

1.02 RELATED SECTIONS<br />

A. Sheet M-1 of the construction documents<br />

B. Sheet E-2 of the construction documents<br />

1.03 REFERENCES<br />

A. NFPA 30A, Section 7.4.7 Gas Detection System<br />

B. UL - Underwriters Laboratory.<br />

1.04 SYSTEM DESCRIPTION<br />

A. General Description:<br />

1. CO Sensor:<br />

a. Provide a remote CO sensor as located on the drawings. The remote CO<br />

sensors shall utilize a solid state sensing element, be microprocessor<br />

based and be both temperature and humidity compensated for long life<br />

and stability. Pilot lights or LED’S (light emitting diodes) shall indicate<br />

1. Unit normal operation/NOT in alarm.<br />

2. High CO/unit in alarm, and<br />

3. shall indicate unit malfunction.<br />

b. In the unit malfunction condition the sensors output shall be fail-safe and<br />

indicate steady high CO condition.<br />

c. The CO sensor range shall be 0 to 250 ppm and shall be calibrated with<br />

a CO test gas and be calibrated to initiate exhaust fan operations at 50<br />

ppm of CO concentration.<br />

2. CO System Controller<br />

a. The CO system controller shall monitor its remote sensor. When a CO<br />

alarm level is detected the controller shall delay exhaust fan contact<br />

closure for 30 seconds. If the high CO conditioned persists for more than<br />

30 seconds the exhaust fan contacts shall close. The minimum fan ON<br />

time shall be field settable from one to eight minutes, in one minute<br />

increments. Should the CO concentration remain above the alarm level<br />

after the minimum run time has timed out, the exhaust fan contacts shall<br />

remain closed (ON) and a second "alarm" set of contacts shall close.<br />

Automatically increase fan speed to meet increasing heating or cooling<br />

demands and to reset the room set temperature when the room<br />

becomes unoccupied.<br />

GAS DETECTION AND ALARM 13850- PAGE 1 OF 5