Bridgestone Retail Operations, LLC<br />

PROJECT MANUAL<br />

Version: January 2012<br />

g. Suppliers of systems not having this feature as functionally specified above shall include a<br />

testing agreement meeting the requirements of NFPA-72 in their base bid quotation. As a<br />

minimum, two (2) years of scheduled testing shall be included.<br />

15. LED Supervision<br />

a. All slave module LEDs shall be supervised for burnout or disarrangement. Should a problem<br />

occur, the panel shall display the module and the LED location numbers to facilitate location<br />

of that LED.<br />

16. Active Status Reminder<br />

a. Should any Alarm, Supervisory, or Trouble condition be present within the system and the<br />

audible signal silenced, the local tone alert shall resound every 8 hours (each change of work<br />

shift) to act as a reminder that the fire alarm system is not 100% operational.<br />

17. Access Levels<br />

a. There shall be a minimum of four (4) access levels. Passcodes shall consist of up to four (4)<br />

digits. Changes to passcodes shall only be made by authorized personnel.<br />

b. Systems not capable of password protected manual command operations shall provide key<br />

operated switches for these functions. Function key switches shall be keyed differently from<br />

any other keyed switches or locks used within the system.<br />

c. In order to maintain security when entering a passcode, the entered digits shall not be<br />

displayed.<br />

d. When a correct passcode is entered, a message indicating acceptance shall be displayed.<br />

The new access level shall be in effect until the operator manually logs out or leaves the<br />

keypad inactive for ten (10) minutes.<br />

e. When an incorrect passcode is entered, a message shall be displayed indicating that the<br />

passcode was invalid<br />

f. Access to a level shall only allow the operator to perform all actions within that level and all<br />

actions of lower levels, not higher levels.<br />

g. The following keys/switches shall have access levels associated with them:<br />

Alarm Acknowledge<br />

Supervisory Acknowledge<br />

Trouble Acknowledge<br />

Alarm Silence<br />

System Reset<br />

18. ALARM SEQUENCE<br />

a. The system alarm operation subsequent to the alarm activation of any manual station,<br />

automatic detection device, or sprinkler flow switch is to be as follows:<br />

b. All audible alarm notification appliances shall sound as required by local authority having<br />

jurisdiction.<br />

c. All visible alarm notification appliances:<br />

Xenon Strobes shall display a continuous synchronized pattern.<br />

d. All doors normally held open by door control devices shall release.<br />

e. A supervised signal to notify the local fire department or an approved central station is to be<br />

activated. To accommodate and facilitate job site changes, the type of "city connection circuit"<br />

is to be determined by the fire alarm equipment supplier and all city tie connection equipment<br />

supplied as required.<br />

f. An alarm is to be displayed on the panel display as defined in the OPERATION section of<br />

these specifications. The alarm LED shall flash on the control panel and the remote<br />

annunciator until the alarm has been acknowledged at the control panel or the remote<br />

annunciator. Once acknowledged, this same LED shall latch on. A subsequent alarm<br />

received from another zone after acknowledged shall flash the alarm LED on the control<br />

panel and the panel display shall show the new alarm information.<br />

g. A pulsing alarm tone shall occur within the control panel and the remote annunciator until<br />

acknowledged.<br />

h. The control panel is to have a dedicated supervisory service LED and a dedicated<br />

supervisory service acknowledge switch.<br />

FIRE ALARM (SCSS REV #3 4-1-10) 17000 - Page 4