Ex. No.<br />

4.6<br />

Description Parameters<br />

The external device monitoring circuit for a dependent, second<br />

OSSD has the same function as the standard external device monitoring<br />

circuit. This circuit monitors the second channel, but does not<br />

have any effect on the enabling of channel 1.<br />

In this example, the magnet contact is monitored by the second<br />

external device monitoring circuit.<br />

The Monitored start - monitor input device requires activation of the<br />

start input of the corresponding OSSD as an additional start requirement.<br />

If the AND link of all the monitoring, linking and external device<br />

monitoring circuit devices of an OSSD delivers an ON result, and if the<br />

start requirements have been fulfilled, the monitored start - monitor<br />

input start device relays the enabling request to the output device.<br />

When the circuit is enabled (ON), the output circuits (2 relays each)<br />

of both OSSDs are simultaneously activated by the Stop category 1-<br />

two relay outputs output device.<br />

When the circuit is switched off (OFF), the output circuit of OSSD 1 is<br />

immediately switched off without a delay. The output circuit of the<br />

dependent OSSD is switched off after the set switch-off delay has<br />

elapsed. The switch-off delay can be set between 0 s and 300 s in<br />

100 ms increments. It is not possible to switch the system on again<br />

until both output circuits have switched off.<br />

124 Functional Example No. CD-FE-I-035-V10-EN