Fault 395 (acceptance test / acknowledgement present)<br />

Fault F395 is output when powering-up for the first time and<br />

after replacing the Control Unit CU or the Power Module PM.<br />

This fault does not represent an incorrect drive inverter function.<br />

The reason for this fault message is to monitor the individual<br />

drive inverter components (CU and PM) to prevent<br />

them from being replaced by unauthorized personnel.<br />

Acknowledging fault F395<br />

To acknowledge the F395 in conjunction with a CU240S DP F,<br />

proceed as follows:<br />

■ Set parameter p0010 to 30<br />

■ Enter the safety password (standard = 12345) into<br />

parameter p9761<br />

■ Set parameter p7844 to 0<br />

■ F395 will no longer be displayed<br />

■ For safety reasons you now have to run an acceptance test.<br />

For more information see the G120 Operation Instructions,<br />

Appendix, Acceptance Log.<br />

For information:<br />

For a CU without safety information it is sufficient to<br />

acknowledge fault F395 using "acknowledge fault"<br />

(SINAMICS G120 terminal strip or PROFIBUS).<br />

Functional Example No. SD-FE-I-001-V11-EN 469<br />