Ex. No.<br />

5<br />

For calculating the max. reaction time of your F-system please<br />

use the Excel file (Cotia table), which is available for S7 Distributed<br />

<strong>Safety</strong> V 5.3. This file is available on the internet:<br />

http://support.automation.siemens.com/WW/view/en/<br />

19138505<br />

Muting<br />

In this example we show parallel muting. Muting is an intended<br />

suppression of the protective function. This is e.g. required<br />

during transporting the material into the danger zone.<br />

Muting is triggered by muting sensors. In this example, FB189<br />

(F_MUTING) is called in the F program (FB 1, DB 1). Among<br />

other things, FB189 as input parameter has the signals of the<br />

four muting sensors (MS_11...MS_22) as well as three parameterizable<br />

times (DISCTIM1, DISCTIM2; TIME_MAX).<br />

MS_11<br />

MS_12<br />

If the muting sensors MS_11 and MS_12 are activated by the<br />

product within the time DISCTIM1, the muting mode is activated.<br />

MS_11<br />

MS_12<br />

Sender<br />

Receiver<br />

Sender<br />

Receiver<br />

MS_21<br />

MS_22<br />

MS_21<br />

MS_22<br />

Hazardous Area<br />

Hazardous Area<br />

The muting mode remains active as long as MS_11 and<br />

MS_12 are activated by the product. The product may pass the<br />

light curtain without causing a stop of the machine.<br />

220 Functional Example No. AS-FE-I-005-V10-EN<br />

G_FB_XX_118<br />

G_FB_XX_119<br />

MS_11<br />

MS_12<br />

Sender<br />

Receiver<br />

MS_21<br />

MS_22<br />

Hazardous Area<br />

Before the muting sensors MS_11 and MS_12 switch inactive,<br />

the muting sensors MS_21 and MS_22 must have been activated<br />

within the time DISCTIM2. This ensures that muting<br />

mode remains active.<br />

The muting mode is terminated, if one of the muting sensors<br />

MS_21 or MS_22 is switched inactive by the product. The<br />

maximum time for the muting mode to be active is<br />

TIME_MAX.<br />

Note<br />

Muting mode also becomes active if the muting sensors<br />

MS_21 and MS_22 respond first.<br />

Active muting operation is indicated by white indicator lights.<br />

In this example, one indicator light is used to display the muting<br />

mode. The diagram below illustrates the relations during<br />

muting mode with regard to time.<br />

MS_11<br />

MS_12<br />

MS_21<br />

MS_22<br />

MS_11<br />

MS_12<br />

t < DISCTIM1<br />

MUTING<br />

Sender<br />

Receiver<br />

MS_21<br />

MS_22<br />

t < DISCTIM2<br />

t < TIME_MAX<br />

Hazardous Area<br />

G_FB_XX_120<br />

G_FB_XX_121<br />

G_FB_XX_122