Ex. No.<br />

12<br />

No. Instructions Response<br />

OUT1 OUT3 K2 K80 MASTERDRIVES<br />

1 Press ACK and release 0 1 1 1 Standstill<br />

2 Press START and release 1 1 1 1 Starts (normal operation)<br />

3 Press STOP and release 0 1 1 1 Shuts down (operational stop)<br />

4 Repetition No. 2 1 1 1 1<br />

5 Press ESTP 0 0 1 1 • Shuts down (fast stop)<br />

time delay • Pulse blocking<br />

X 0<br />

• X: K2=1, if no readback error of option K80 (otherwise K2=0)<br />

6 Unlock emergency-stop button<br />

0 0 1 0<br />

7 Press ACK and release 0 1 1 1 Edge change from 0 to 1 at OUT3 is a prerequisite for OUT1 to be reset.<br />

8 Repetition No. 2 1 1 1 1<br />

9 SIM_FDOR=0: Open safety 0 0 1 1 • Shuts down (fast stop)<br />

door (simulated by pulling the<br />

position switch)<br />

time delay<br />

X 0<br />

• Pulse blocking<br />

• X: K2=1, if no readback error of option K80 (otherwise K2=0)<br />

10 SIM_FDOR=1: Close safety<br />

door<br />

0 0 X 0 Standstill<br />

11 Press ACK and release 0 1 1 1 Edge change from 0 to 1 at OUT3 is a prerequisite for OUT1 to be reset.<br />

12 Set REQ_SG to 1 0 1 1 1 Operating mode "safe speed" (SG) has been set<br />

13 Press DMS and keep it pressed 1 1 1 1 Operating mode "safe speed" (SG) active<br />

14 SIM_FDOR=0: Open safety 1 1 1 1 In operating mode "safe speed" (SG) the safety door can also be<br />

door (simulated by pulling the<br />

position switch)<br />

opened at active drive.<br />

15 Release DMS 0 1 1 0 Shuts down to safe standstill<br />

Note<br />

An acknowledgement signal is required for starting the<br />

machine:<br />

• Prior to the first start (normal operation)<br />

• After triggering emergency stop<br />

• After opening the safety door in normal operation<br />

• After error recognition during plausibility checks for the<br />

speed value<br />

Important hardware component settings<br />

Below, several important settings from the hardware configuration<br />

of STEP 7 are shown to provide you with an overview.<br />

These settings are available in the included STEP 7 project. It<br />

is basically possible to change these settings (e.g. due to individual<br />

requirements), but please consider the following note:<br />

376 Functional Example No. AS-FE-I-012-V10-EN<br />

Attention<br />

The settings shown below contribute to meet the requirements<br />

of category 3 according to EN 954-1 and<br />

SIL 2 of IEC 62061. Changes at the settings may cause<br />

loss of the safety function.<br />

If you implement changes (e.g. add an additional module),<br />

the sample code has to be adapted accordingly.