Ex. No.<br />

11 Basic Performance Data<br />

Load memory and main memory<br />

Determining the memory parameters:<br />

■ Open STEP 7 project of the functional example in the<br />

SIMATIC Manager<br />

■ Determine load memory and main memory for all blocks in<br />

the block container<br />

Runtimes<br />

Total Standard<br />

blocks<br />

F blocks<br />

(fail-safe)<br />

Load Memory 56.5 KByte 1.2 KByte 55.3 KByte<br />

Main Memory 39.1 KByte 0.5 KByte 38.6 KByte<br />

Time Note<br />

Total cycle time (standard minimum 1ms Read from S7-CPU<br />

program and safety program)<br />

maximum 12ms<br />

Maximum runtime safety program 13ms Calculated with<br />

Cotia table<br />

Determining the total cycle time:<br />

■ Load STEP 7 project into S7-CPU, set S7-CPU to run, and<br />

operate the functional example.<br />

■ Read the measured cycle time in the "Module Information<br />

CPU / Scan Cycle Time" tab<br />

Determine max. runtime of the safety program:<br />

■ The value is calculated with the Cotia table for<br />

"S7 Distributed <strong>Safety</strong>" V5.4.<br />

This file is available on the internet:<br />

http://support.automation.siemens.com/ww/view/en/<br />

21627074<br />

326 Functional Example No. AS-FE-I-011-V10-EN