Ex. No.<br />

11 Operation: F-communication error<br />

Operating in the following table shows the procedure:<br />

■ Pulling the PROFIBUS DP cable from the F-CPU<br />

■ Restoring the connection<br />

■ Reintegration<br />

A more detailed description of the scenario, with overview image<br />

on the hardware setup, is available at page 331.<br />

Step<br />

Action<br />

Comment Indicator light / SF-LED<br />

A: REQ_ACK_ESTP_ACTUATOR<br />

B: PASSIVATION_ON<br />

C: REQ_ACK_PASS_ACTUATOR<br />

D: ACTUATOR<br />

E: TEST<br />

F: SF-LED of F-DI and F-DO module<br />

A B C D E F<br />

--- --- 11 This is the initial state for the following<br />

operations.<br />

0 0 0 1 1 0<br />

1 Removing the PROFIBUS DP cable - 0 0 0 0 0 0 (*2)<br />

2 Restoring the connection - 0 1 0 0 0 0 (*3)<br />

Press ACK_PASS_ACTUATOR 10 After acknowledgement by the user,<br />

the F-I/O-module is reintegrated.<br />

1 0 0 0 1 0<br />

Explanations on the table:<br />

(*1):<br />

At page 334 you find an overview of statuses and mode transitions<br />

of the sample code.<br />

(*2):<br />

The BF-LED at "IM 151 HF" lights up. The BF-LED at "IM 151 HF"<br />

is blinking.<br />

(*3):<br />

The BF-LEDs are off.<br />

346 Functional Example No. AS-FE-I-011-V10-EN<br />