Ex. No.<br />

9 Flowchart<br />

The following flow chart shows the functionality at the example<br />

of group 1 (motor M1) and the group shutdown. The same<br />

procedure applies to group 2 (motor M2); only M1 and M2<br />

need to be exchanged and K1, K2 be replaced with K3, K4.<br />

N<br />

N<br />

N<br />

J<br />

N<br />

Start<br />

M1 running?<br />

Common emergency<br />

stop unlocked?<br />

J<br />

Emergency stop1<br />

unlocked?<br />

J<br />

Readback signal K1<br />

and K2 OK?<br />

J<br />

Acknowledgement<br />

necessary?<br />

N<br />

Start command M1?<br />

J<br />

M1 starts<br />

J<br />

Common emergency<br />

stop unlocked?<br />

Time sequence for single/group shutdown<br />

To illustrate the process, the time sequence during a single<br />

and a group shutdown is shown below. The names at the ordinates<br />

correspond to the names in the program code.<br />

Designation Explanation<br />

START_M1 Start command for motor 1 (group 1).<br />

START_M2 Start command for motor 2 (group 2).<br />

ACK_ALL Acknowledgement for all groups<br />

ESTP1 Emergency stop for motor M1 (group 1)<br />

ESTP2 Emergency stop for motor M2 (group 2)<br />

ESTP_ALL Emergency stop for all groups<br />

M1 Motor 1 (group 1)<br />

M2 Motor 2 (group 2)<br />

278 Functional Example No. AS-FE-I-009-V10-EN<br />

J<br />

Emergency stop1<br />

unlocked?<br />

J<br />

N<br />

N<br />

M2 stops<br />

J<br />

Readback signal K1<br />

and K2 OK?<br />

N<br />

Time<br />

t1 t2 t3<br />

Explanation<br />

t4 t5 t6 t7 t8 t9 t10<br />

M1 stops<br />

G_FB_XX_083<br />

START_M1<br />

(NO)<br />

START_M2<br />

(NO)<br />

G_FB_XX_164<br />

ACK_ALL<br />

(NO)<br />

ESTP1<br />

(NC)<br />

ESTP2<br />

(NC)<br />

ESTP_ALL<br />

(NC)<br />

M1<br />

M2<br />

t1 An acknowledgement is required before starting for the<br />

first time.<br />

t2 Start command for motor M1. Motor M1 starts.<br />

t3 Start command for motor M2. Motor M2 starts.<br />

t4 Emergency stop triggered for group 1 Motor M1 stops.<br />

t5 Emergency stop triggered for group 2 Motor M2 stops.<br />

t6 Unlocking both pressed emergency stop buttons.<br />

t7 Acknowledgement is necessary prior to every restart.<br />

t8 Start command for motor M1. Motor M1 starts.<br />

t9 Start command for motor M2. Motor M2 starts.<br />

t10 Emergency stop, applying to all groups, is activated and<br />

switches all groups off.<br />

Note<br />

Apart from the acknowledge button applying to all<br />

groups, each group as a respective acknowledge button<br />

(not displayed in the above time sequence).<br />

Advantages/customer benefits<br />

■ Wiring reduced to a minimum due to use of failsafe S7-CPU<br />

and distributed I/O. Dieser Vorteil kommt um so mehr zum<br />

Tragen, je mehr Sicherheitsfunktionen realisiert werden.<br />

■ Programming the failsafe program with STEP 7 engineering<br />

tools.<br />

■ Only one CPU is required, since failsafe and standard program<br />

parts run on a coexistent basis in the CPU<br />

■ Use of prefabricated (and certified) failsafe blocks from the<br />

Distributed <strong>Safety</strong> library.<br />