Process: <strong>Safety</strong> program<br />

Precondition<br />

The user can passivate and automatically reintegrate F-modules<br />

via the safety program. The PASS_ON variable is used for<br />

this.<br />

State<br />

F-module not passivated (1)<br />

In the safety program: PASS_ON = 1<br />

F-module passivated (2)<br />

In the safety program: PASS_ON = 0<br />

F-module reintegrated (3)<br />

Process sequences<br />

The F-module is passivated with "PASS_ON = 1". The F-module<br />

is automatically reintegrated with "PASS_ON = 0".<br />

The following figure and table illustrates the process sequence.<br />

Number in brackets indicates the state.<br />

Description of status and events F-I/O data block<br />

F-DI and F-DO / SF-LED<br />

A: ACK_NEC<br />

B: ACK_REI<br />

C: PASS_OUT<br />

D: QBAD<br />

E: ACK_REQ<br />

F: SF-LED<br />

A B C E<br />

1 F-module is not passivated. 0 0 0 0<br />

Event: User sets "PASS_ON = 1" in the safety program 1<br />

2 F-system has passivated the F-module.<br />

Event: User sets "PASS_ON = 0" in the safety program.<br />

1 0 1 0<br />

3 F-system has reintegrated the F-module. 0 0 0 0<br />

Functional Example No. AS-FE-I-011-V10-EN 361<br />

Ex. No.<br />

11