2 safety circuits in a cascade according to Category 4 in<br />

compliance with EN 954-1<br />

(PM-D F X1 and Failsafe Motor Starter )<br />

with ET200S <strong>Safety</strong> Motor Starter Solution Local<br />

Function<br />

Description of the functionality<br />

If people (in production technology) are close to machines,<br />

then they must be protected using the appropriate equipment.<br />

The EMERGENCY STOP command device represents a<br />

widely established component that protects man, machine<br />

and environment against potential hazards.<br />

This safety function example will show how a cascaded<br />

EMERGENCY STOP shutdown with 2 motor starter groups can<br />

be implemented in an ET200S station.<br />

A PM-D F X1 safety module can provide a total of 6 safetyrelated<br />

shutdown groups (refer to the ET200S Motor Starter<br />

Manual) by accessing the SG1 to SG6 buses (safety groups) of<br />

the Failsafe Motor Starter. It routes the safety-related control<br />

voltage of the safety shutdown groups SG1 to SG6 to the SG<br />

rail of the terminal module of the next Failsafe Motor Starter.<br />

The terminal modules of the Failsafe Motor Starter additionally<br />

have a coding block. This allows the motor starter to be<br />

assigned one of the six safety-related shutdown groups (refer<br />

to page 67). The shutdown is realized by a safety relay switching<br />

one of the 6 SG buses into a no-voltage condition.<br />

The first two motor starters (refer to page 66) are, in this function<br />

example, connected to SG1 - the others to SG2. The motor<br />

starters can be shutdown in a safety-related fashion by<br />

shutting down an SG.<br />

The EMERGENCY STOP command devices with positivelyopening<br />

contacts are monitored by the 3TK2841 safety relays.<br />

If the EMERGENCY STOP of group 1 is actuated, then the<br />

3TK2841 (K1) shuts down its enable circuit according to stop<br />

Category 0 according to EN 60204-1. The SG1 and the<br />

3TK2841 (K2) are shutdown. The 3TK2841 (K2) in turn shuts<br />

down the SG2.<br />

If the EMERGENCY STOP of group 1.1 is actuated, the 3TK2841<br />

(K2) shuts down its enable circuit according to stop Category<br />

0 in compliance with EN 60204-1. SG2 is shutdown.<br />

Drives are stopped in this particular function example. Before<br />

restarting or acknowledging the EMERGENCY STOP shutdown<br />

using the start button, it is checked as to whether the contacts<br />

of the EMERGENCY STOP commanding device are closed.<br />

This functional example only discusses the safety function.<br />

The motor starter is operationally switched using a standard<br />

PLC and is not considered any further here.<br />

Note<br />

Equipment, functional aspects and design guidelines<br />

for EMERGENCY STOP command devices are provided<br />

in EN 418.(EN ISO 13850 in draft status).<br />

Functional Example No. CD-FE-I-029-V10-EN 63<br />