Ex. No.<br />

4<br />

Timing diagram<br />

As an illustration, points 1 to 10 from the preceding table are illustrated<br />

in the following time diagram. The time axis contains<br />

numbers 1 to 10, which refer to the numbers in the table.<br />

SW1<br />

SW2<br />

ACK<br />

START<br />

STOP<br />

ACTUATOR<br />

1<br />

2 3 4 5 6 7 8 9 10<br />

212 Functional Example No. AS-FE-I-004-V10-EN<br />

t<br />

t<br />

t<br />

t<br />

t<br />

t<br />

G_FB_XX_110<br />

Important hardware component settings<br />

Below, several important settings from the hardware configuration<br />

of STEP 7 are shown to provide you with an overview.<br />

These settings are available in the included STEP 7 project. It<br />

is basically possible to change these settings (e.g. due to individual<br />

requirements), but please consider the following note:<br />

Warning!<br />

The settings shown below contribute to meet the requirements<br />

of <strong>Safety</strong> Category 4. Changes at the settings<br />

may cause loss of the safety function.<br />

If you implement changes (e.g. add an additional module),<br />

the sample code has to be adapted accordingly.<br />

Overview picture<br />

The PROFIBUS adress at IM 151HF is set using DIP-switches.