Ex. No.<br />

11 Process: F-communication error<br />

Note<br />

For "F-communication error" automatic reintegration<br />

is not possible!<br />

Precondition<br />

In the safety program the user acknowledges the reintegration<br />

by providing ACK_REI with a positive edge.<br />

State<br />

F-I/O not passivated (1)<br />

Error occurs<br />

F-I/O passivated (2)<br />

Error occurs<br />

F-I/O remains passivated (3)<br />

User acknowledged<br />

F-I/O reintegrated (4)<br />

Explanations for the table:<br />

(*1): BF-LED at IM 151 HF is on. BF-LED at F-CPU is blinking.<br />

(*2): The BF-LEDs are off.<br />

360 Functional Example No. AS-FE-I-011-V10-EN<br />

Process sequences<br />

At F-communication error (e.g. due to disconnecting F-CPU<br />

and ET200) the entire affected F-I/O is passivated. If the error<br />

has been removed the F-I/O is only reintegrated after acknowledgement<br />

by the user. This applies irrespective of the<br />

ACK_NEC value. The following figure and table illustrates the<br />

process sequence.<br />

Numbers in brackets indicate the state.<br />

Description of status and events F-I/O data block<br />

F-DI and F-DO / SF-LED<br />

A: ACK_NEC<br />

B: ACK_REI<br />

C: PASS_OUT<br />

D: QBAD<br />

E: ACK_REQ<br />

F: SF-LED<br />

A B C D E F<br />

1 F-I/O is not passivated.<br />

Event: Error occurs.<br />

x 0 0 0 0 0<br />

2 F-module is passivated.<br />

Event: Error removed.<br />

x 0 1 1 0 0 (*1)<br />

3 F-I/O has recognized that the error has been removed. x 0 1 1 1 0 (*2)<br />

Event: User acknowledges (positive edge). 0->1<br />

4 F-system has reintegrated the F-I/O. x x 0 0 0 0