Ex. No.<br />

4<br />

Hardware component wiring<br />

Safe stop is activated in the drive system through the selection<br />

of two terminals (motor module and CU). These two clamps<br />

have to be connected to a fail-safe digital output module.<br />

The following connection example illustrates the connection<br />

of a positive switching ET 200 output with a CU input. Another<br />

output switches the EP terminal at the motor module.<br />

Component wiring<br />

Software Required<br />

The program supplied with the Installation Guide has been<br />

created with the following software releases of the Engineering<br />

Tools resp. Runtime Systems:<br />

■ STEP7 V5.4 SP1<br />

■ Distributed <strong>Safety</strong> V5.4 (S7 F Configuration Pack V5.5)<br />

■ SCOUT V4.0<br />

■ STARTER V2.3<br />

■ SIMOTION FW V4.0<br />

■ SINAMICS FW V2.4.<br />

440 Function Example No. MC-FE-I-004-V11-EN<br />

Communication Configuration and Interface Description<br />

The F-CPU controller communicates with SIMOTION via a bus<br />

connection (slave) resp. via a transceiver. The scope of transmit<br />

and receive words per axis has to be set up as shown in the<br />

following figure. It is configured in the HW Config of the<br />

SIMATIC Manager.