Ex. No.<br />

2<br />

Settings of the failsafe F-DI<br />

The settings are displayed after double-clicking "4/8 F-DI<br />

DC24V" (see "Overview picture").<br />

DIL switch settings<br />

This value has to be set on the module (F-DI).<br />

F monitoring time<br />

It has to be observed that the F monitoring time must be<br />

larger than the call time of OB 35.<br />

Also in the "Parameter" tab.<br />

The safety position switch is assigned to channel 0, the hinge<br />

switch to channel 4 and the simulation of the speed or standstill<br />

monitor to channel 1. All three sensors are connected as<br />

single-channel. The other channels are deactivated.<br />

186 Functional Example No. AS-FE-I-002-V10-EN<br />

Settings of the failsafe F-DO<br />

The settings are displayed after double-clicking "4 F-DO<br />

DC24V/2A" (see "Overview picture").<br />

DIL switch settings<br />

This value has to be set on the module (F-DI).<br />

F monitoring time<br />

It has to be observed that the F monitoring time must be<br />

larger than the call time of OB 35.<br />

Activate used channels, deactivate channels which are not<br />

used. The read-back time defines the duration of the switchoff<br />

procedure for the respective channel. If the respective<br />

channel switches high capacity loads, the read back time<br />

should be set sufficiently large. We recommend setting the<br />

read back time as small as possible, however large enough so<br />

that the output channel does not become passive.