F-I/O-module data block<br />

What is an F-I/O-module data block<br />

For every F-I/O-module one data block is automatically generated<br />

during compilation in the STEP 7 hardware configuration.<br />

The F-I/O-module data block is the interface between the user<br />

program and the F-system. Control and status information of<br />

the F-I/O-module are exchanged via the interface.<br />

The F-I/O-module data block contains variables which can be<br />

accessed by the safety program as well as the standard program.<br />

The F-I/O-module data block does not contain any process<br />

values. The process values are located in the process image<br />

of the F-CPU.<br />

In standard program read<br />

In the safety program read and write<br />

Access to the F-I/O-module<br />

data block<br />

The following figure illustrates the relationships.<br />

Functional Example No. AS-FE-I-011-V10-EN 349<br />