Setup and Wiring<br />

In order to set up and wire the functional example, it is absolutely<br />

necessary to consider the following note:<br />

Warning!<br />

In order to meet the requirements of <strong>Safety</strong> Category<br />

4, it is obligatory to read back the process signal to the<br />

actuator. Read back is not implemented in this example.<br />

The actuator in this example is an indicator light simulating<br />

a machine. If other actuators are used, read back<br />

has to be ensured by the user. The <strong>Safety</strong> <strong>Integrated</strong><br />

Functional Example AS-FE-I-007-V10-EN provides a detailed<br />

description of "Read back".<br />

An overview of the hardware structure<br />

The arrangement to implement the safety door consists of a<br />

PROFIBUS configuration. A failsafe S7-CPU is used as DP master,<br />

an ET 200S as DP slave. The yellow indicator light can be replaced<br />

by actuators in accordance with their requirements.<br />

Below, the wiring of conventional modules is shown only partly<br />

to provide greater clarity.<br />

PS<br />

307<br />

Acknowledgement<br />

START<br />

STOP<br />

CPU<br />

315F<br />

DP<br />

F-DI<br />

2DI HF<br />

IM 151<br />

HF<br />

PM-E<br />

Position<br />

switch<br />

4DI<br />

HF<br />

PM-E F-DO<br />

F-DI<br />

Position<br />

switch<br />

Note<br />

The "high feature" electronic modules can also be replaced<br />

by standard modules.<br />

Aktuator<br />

Wiring of the hardware components<br />

Requirements: The power supplies are supplied with 230V AC.<br />

First check the addresses set at the hardware components<br />

listed below:<br />

Hardware<br />

component<br />

IM 151 High<br />

Feature<br />

Einzustellende<br />

Adress<br />

6 (PROFIBUS address)<br />

F-DI Switch position:<br />

1111111110<br />

F-DO Switch position:<br />

1111111101<br />

Note<br />

Can be changed<br />

The PROFIsafe addresses are<br />

automatically assigned during<br />

configuring the failsafe<br />

modules in STEP 7. The<br />

PROFIsafe addresses 1 to<br />

1022 are permissible. Please<br />

make sure that the setting at<br />

the address switch (DIL<br />

switch) on the side of the<br />

module corresponds to the<br />

PROFIsafe address in the<br />

hardware configuration of<br />

STEP 7.<br />

Note<br />

The DP interface of the CPU 315F must be connected<br />

with the DP interface of the IM 151 HF.<br />

Note<br />

The wiring of the hardware is illustrated below. In the<br />

following table, the hardware components occurring<br />

several times are numbered so they can be allocated in<br />

the subsequent wiring plan.<br />

Functional Example No. AS-FE-I-004-V10-EN 209<br />

Ex. No.<br />

4