Ex. No.<br />

11 Overview of the signals of the network:<br />

Signal Source / Target Meaning<br />

ACK_PASS_ACTUTOR From process (button) Acknowledgement by the user for manual reintegration<br />

F00007_4_F_DO_DC24V_2A.ACK_REI To F-I/O-module data block of F-DO If "0->1":<br />

F-DO is reintegrated.<br />

F00001_4_8_F_DI_DC24V.ACK_REI To F-I/O-module data block of F-DI If "0->1":<br />

F-DI is reintegrated.<br />

Description of the network function:<br />

F-DO and F-DI are reintegrated after acknowledgement by the<br />

user:<br />

■ Manual reintegration of the F-DO is necessary in the sample<br />

code after channel or F-communication error.<br />

■ Manual reintegration of the F-DI is necessary in the sample<br />

code only after F-communication error.<br />

Description: FB 215, DB1 (F_ESTOP1)<br />

The block is a TÜV certified application block from the Distributed<br />

<strong>Safety</strong> library.<br />

Function and parameter of the F-blocks:<br />

■ See STEP 7 online-help<br />

Operating instruction on the sample code<br />

This chapter describes the operation of the functional example.<br />

The operation is divided into different scenarios<br />

Scenario Page<br />

Normal operation 343<br />

Manual reintegration after wire-break at F-DO 344<br />

Automatic reintegration after wire-break at<br />

F-DI<br />

345<br />

Reintegration after F-communication error 346<br />

342 Functional Example No. AS-FE-I-011-V10-EN<br />

The following prerequisites must be fulfilled in order to operate<br />

the functional example:<br />

■ The hardware configuration, the standard program, and<br />

the safety program are located on the F-CPU<br />

■ Emergency stop unlocked<br />

As a description, tables with uniform structure are used below.<br />

The columns of the table have the following meaning:<br />

Column name Column content<br />

"Step" Number of the operational step<br />

"Action" Action of user<br />

"State" The number marks the state reached after executing<br />

the action. An overview of all status is<br />

available at page 334.<br />

"Comment" Comments on the step.<br />

"Indicator Here the switch status of the five indicator<br />

light"<br />

lights and the SF LED is depicted which is set<br />

after executing the action. Switched indicator<br />

lights are marked with "1". (*1)<br />

"SF-LED" The column indicates the status of the collective<br />

error display on the F-I/O-module (red<br />

LED). (*1)<br />

(*1): To recognize more clearly which bits change during a<br />

mode transition, they are shaded in gray: If a bit is shaded<br />

gray, it has changed compared with its previous state.