Ex. No.<br />

5.1<br />

■ This means that a value of 200 must be entered for<br />

F_WD_Time.<br />

<strong>Siemens</strong> telegram 352, PZD 6/6<br />

The standard control (control word, frequency setpoint etc.)<br />

of SINAMICS G120 is implemented using the <strong>Siemens</strong> telegram.<br />

In SINAMICS G120, instead of telegram 352 (fixed assignment<br />

of the con-trol/feedback signal words), telegram 999 is used<br />

(free assignment of the control/feedback signal words).<br />

In this case, in SINAMICS G120, to start, telegram type 350<br />

should be selected in parameter p922. This pre-assigns the<br />

BICO connections. Telegram type 999 (free interconnection<br />

via BICO) should then be selected and the following interconnections<br />

made:<br />

■ p2051[4] = r2131 (error number)<br />

■ p2051[5] = r2110 (alarm number)<br />

In order that SINAMICS G120 can use the safety functions in<br />

the safety program, symbolic addresses must be assigned for<br />

the inputs and outputs of the PROFIsafe module. The input<br />

window for the symbolic addresses is opened by selecting the<br />

PROFIsafe module, pressing the righthand mouse key and selecting<br />

Edit symbols...<br />

482 Functional Example No. SD-FE-I-001-V11-EN<br />

Only the inputs and outputs listed in this example are relevant<br />

for communications.<br />

Functions of the STEP 7 program (without safety program)<br />

Program overview<br />

The STEP 7 program essentially comprises blocks FC10, FC100<br />

and DB1 that are called in the cyclic program (OB1).