This communication is realized via PROFIBUS. This enables<br />

■ transferring the setpoint speed value to MASTERDRIVES<br />

■ detecting the actual speed value of MASTERDRIVES.<br />

DP slave (I-Slave)<br />

An ET 200S with intelligent and fail-safe interface (IM 151-7F-<br />

CPU) is used.<br />

Note<br />

In this example, the IM 151-7F CPU has already been<br />

configured as DP slave. However, if you require information<br />

for integrating an intelligent IM 151 interface<br />

as DP slave, please refer to the manual "ET 200S - Interface<br />

Module IM 151-7 CPU" (Entry-ID: 12714722)<br />

The I-Slave realizes the following functionalities:<br />

Safe drive shut down<br />

The drive is switched off safely for<br />

■ Triggered emergency stop<br />

■ Opening the safety door in normal operation<br />

■ Error during speed monitoring in "safe speed" (SG) mode<br />

If one of these cases occurs, the drive is stopped immediately:<br />

The fail-safe output of the F-DO is connected with the OUT3<br />

contact at MASTERDRIVES. At negative edge, OUT3 switches<br />

off the operation as fast as possible (fast stop).<br />

Note<br />

Fast stop is generally no primary safety function.<br />

However it enhances safety and helps reduce kinetic<br />

energy. OUT3 can also be connected to MASTERDRIVES<br />

via a standard module. The reason behind using OUT3<br />

via an F-DO in this example is that otherwise an additional<br />

standard output module for ET 200S would be<br />

required.<br />

Reaching category 3 according to EN 954-1 requires two different<br />

methods for safe shut down:<br />

■ Option K80 for MASTERDRIVES<br />

■ Shutdown by contactor<br />

Option K80 (shut down method 1)<br />

Option K80 for MASTERDRIVES contains a fail-safe relays with<br />

positively driven feedback contact, which shuts down power<br />

supply for controlling the power transistors (IGBTs). Pulse<br />

blocking occurs<br />

■ in case of an error with delay after fast stop (OUT3=0) via<br />

the F-DO<br />

■ in operating mode "safe speed" (SG) and drive standstill.<br />

Shutdown by line contactor (shutdown method 2)<br />

If an error is detected during evaluating the feedback contact<br />

of option K80, the contactor disconnects the drive from the<br />

network. If there is no readback error at option K80, the drive<br />

remains connected to the network; category 3 according to<br />

EN 954-1 remains true.<br />

Functional Example No. AS-FE-I-012-V10-EN 365<br />